| Plan Review Notes For Permit 03051238 |
| Permit Number |
03051238 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2003-05-21 00:00:00 | *********** UNSAT *************** | | | | | | 1)NOTE: PLEASE SEE WIND LOAD DETAIL FOR | | | LIGHT POLES SHOWN AT 120 MPH. PLEASE SEE | | | FBC FOR 140 MPH MIN. PLEASE SUBMIT | | | DETAIL FOR THIS. | | | | | | 2)NOTE: PLEASE CLARIFY HEIGHT REQ`MENTS | | | FOR ADA FHAR,24 CFR 100.205 | | | | | | 3)NOTE: AS PER LOCAL AMENDMENTS 310-2(B) | | | 1&2. NO ALUM CONDUCTORS SMALLER THAN | | | #2. PLEASE ALSO NOTE THAT ALUM IS NOT | | | PERMITTED FOR GROUNDING OR BODNING. | | | | | | 4)NOTE: PLEASE SEE UNIT "C" E-43 | | | PLEASE SEE MISSING SD OUTSIDE BEDROOM. | | | UNIT "B" E-42 | | | | | | 5)NOTE: PLEASE SEE SOME UNIT LAYOUTS ARE | | | MISSING ROOM DESIGNATIONS. | | | | | | 6)NOTE: PLEASE SHOW ALL CONTINUOUS LOADS | | | AT 125% (HOUSE). 215-3/230-42 | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-805-6717 | | | [email protected] | | | | | | PLEASE NOTE THAT ALL OTHER BLDG TYPES, | | | SITE/ AMEND AND CLUBHOUSE TO BE UNDER | | | SEPARATE PERMITS. |
|