Plan Review Notes
Plan Review Notes For Permit 03051238
Permit Number 03051238
Review Stop E
Sequence Number 1
Notes
Date Text
2003-05-21 00:00:00*********** UNSAT ***************
  
 1)NOTE: PLEASE SEE WIND LOAD DETAIL FOR
 LIGHT POLES SHOWN AT 120 MPH. PLEASE SEE
 FBC FOR 140 MPH MIN. PLEASE SUBMIT
 DETAIL FOR THIS.
  
 2)NOTE: PLEASE CLARIFY HEIGHT REQ`MENTS
 FOR ADA FHAR,24 CFR 100.205
  
 3)NOTE: AS PER LOCAL AMENDMENTS 310-2(B)
 1&2. NO ALUM CONDUCTORS SMALLER THAN
 #2. PLEASE ALSO NOTE THAT ALUM IS NOT
 PERMITTED FOR GROUNDING OR BODNING.
  
 4)NOTE: PLEASE SEE UNIT "C" E-43
 PLEASE SEE MISSING SD OUTSIDE BEDROOM.
 UNIT "B" E-42
  
 5)NOTE: PLEASE SEE SOME UNIT LAYOUTS ARE
 MISSING ROOM DESIGNATIONS.
  
 6)NOTE: PLEASE SHOW ALL CONTINUOUS LOADS
 AT 125% (HOUSE). 215-3/230-42
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]
  
 PLEASE NOTE THAT ALL OTHER BLDG TYPES,
 SITE/ AMEND AND CLUBHOUSE TO BE UNDER
 SEPARATE PERMITS.