2003-06-07 00:00:00BUILDING PLAN REVIEW
 PERMIT: 03051238
 ADD:750 WEST EXECUTIVE CENTER DRIVE
 CONT:PLAN REVIEW
 CONTACT: EXECUTIVE TRUST, LTD
 TEL: (561)547-0270
 (561)547-5512
 FL BLD CODE= 2001 FLORIDA BUILDING CODE
  
 ACTION: DENIED
  
 GENERAL SITE COMMENTS:
  
 NOTE: PLANS, SPECIFICATIONS, REPORTS OR
 OTHER DOCUMENTS PREPARED BY THE DESIGN
 PROFESSIONAL AND BEING FILED FOR PUBLIC
 RECORD SHALL HAVE THE SIGNATURE AND
 SEAL OF THE DESIGN PROFESSIONAL AFFIXED
 TO THE DOCUMENT.
 FL STATE STAT: 61G15-23.002 ENGINEERS
 FL ATATE STAT: 61G16.003 ARCHITECTS
  
  
 1) PROVIDE NOC RECORDED WITH THE CLERK
 OF COURT BEFORE A PERMIT CAN BE ISSUED.
 PROVIDE PROOF OF OWNERSHIP. THE P. B. C.
 COUNTY PROPERTY APPRAISERS OFFICE
 INDICATES DIFFERENT OWNERSHIP.
  
 2) PROVIDE RECORDED PLAT, AND SITE PLAN
 WITH THE APPROVED STREET NAMES,
 INDICATEALL SITE AMENITIES.
  
 3) FAIR HOUSING: PROVIDE THE SITE PLAN
 THAT CONFIRMS TO THE FAIR HOUSING
 GUIDELINES FOR MULTI HOUSING. AN
 ACCESSIBLE ROUTE TO ALL BUILDINGS,
 AMENITIES,
 ED PUBLIC TRANSPORTATION ETC.LEASING
 OFFICE REQUIRES HANDICAPPED PARKING.
  
 4) MISSING SITE AMENITIES PACKAGE!
 A) GAZEBO
 B) TRASH COMPACTOR
 C) ENTRY GATES OR GUARDHOUSE
 D) SIGNAGE AND IF WALLS OF FENCE
 AROUND THE PROPERTY
 E) INFORMATION FOR FOUNTAIN IN LAKE
 WHERE THE ELECTRIC WILL BE PULLED
 FROM ETC...SRPERATE PERMIT REQUIRED
  
 5) POOL "EFFECTIVE BARRIER" SEE ZONING
 REQUIREMENTS AS WELL AS 424.1 PUBLIC
 SWIMMING POOLS 64E-9.002 EFFECTIVE
 BARRIERS: SEPERATING THE POOL FROM ALL
 OTHER AREAS INCLUDING THE INTERIOR OF
 THE
 CLUBHOUSE AND POOL AREA.
  
 GENERAL INFORMATION:REQUIRED 1606.1.4
  
 5)1606.1.4(1) IN WIND BORNE DEBRIS
 REGIONS, EXTERIOR GLAZING THAT RECEIVES
 POSITIVE PRESSURE IN BUILDINGS SHALL BE
 ASSUMED TO BE OPENINGS UNLESS SUCH
 GLAZING IS IMPACT RESISTANT OR
 PROTECTEDWITH AN IMPACT RESISTANT
 COVERING MEET- ING THE REQUIREMENTS OF
 SSTD 12, ASTM
 E 1886 AND ASTM E 1996 OR MIAMI-DADE.
 1) GLAZED OPENINGS LOCATED WITHIN 30
 FTOF GRADE SHALL MEET THE REQUIREMENTS
 OF LARGE MISSLE TEST.
  
 6) FL BLD CODE 1606.1.5: COMPONENTS &
 CLADDING, PROVIDE 2 COPIES(3 IF THRESH-
 OLD OR RESIDENT INSPECTOR) OF PRODUCT
 TESTING REPORT, SBCCI OR DADE COUNTY
 REPORT ARE ACCEPTED. MISSING REPORTS:
 A) WINDOWS, SINGLE HUNG, CASEMENT,
 FIXED OR HORIZONTAL ROLLER
 B) DOORS, GLAZED AND SOLID DOORS
 OR SLIDING DOORS OR OVERHEAD
 C) STORM SHUTTERS A COPY OF THE CITYS
 IMPLEMENTSTION STANDARD FOR HURRI-
 CANE MISSLE IMPACT PROTECTION WILL
 PROVIDED EXPLAINING THE STANDARD
 FOR LARGE PROJECTS AND A SAMPLE
 ATTACHMENT SCHEDULE.
 D) ROOF ASSEMBLIES PRODUCT TESTING
 REPORT.
  
 7)SITE SPECIFIC ENGINEERING (PRODUCT
 APPROVAL) REQUIRES THE WET SIGNATURE,
 DATE AND EMBOSSED SEAL OF THE ENGINEER
 CERTIFYING THE PRODUCT AND SIGNATURE
 AND SEAL OF THE DESIGN PROFESSIONAL
 OF RECORD.
  
 8)1707.4.5.1 MULLIONS OCCURRING
 BETWEEN INDIVIDUAL WINDOW AND GLASS
 DOOR ASSEMBLIES. TESTING REPORTS ARE
 REQUIRED BY AN APPROVED TESTING
 LABORATORY OR BE ENGINEERED.
  
 9)1707.4.5.2 MULLIONS SHALL BE
 DESIGN-ED TO TRANSFER THE DESIGN
 PRESSURE LOADSAPPLIED BY THE WINDOW OR
 DOOR ASSEMBLIESTO THE ROUGH OPENING
 SUBTRATE.
  
 10)PROVIDE STORM PANEL INFORMATION WITH
 INSTALLATION SCHEDULE AND KEY PLAN WITH
 SPECIFIC ANCHORS AND MOUNTING TO BE
 USEDFOR ALL NON-IMPACT GLAZING.
 FBC 1606.1.4.
  
 11)FL BLD CODE 2001 SECTION 103.6,
 1606.1.4, 1707.4 & 3401.7.2.4.
 PROCEDURES: 1(B) A COMPLETE
 INSTALLATIONSCHEDULE SUMMARIZING &
 IDENTIFYING
 OPENING SIZES, STORY HEIGHTS, UNIT MARK
 NUMBERS, UNIT SPANS/WIDTHS, UNIT STORM
 BAR REINFORCING REQUIREMENTS, WALL
 PRES-SURE ZONES, SLAT TYPES, ETC.,
 SHALL BE
 SUBMITTED AT TIME OF PERMIT APPLICATION
 TO FACILITATE PLAN REVIEW AND PERMIT
 ISSUANCE.
  
 12) ROOF ASSEMBLIES: 1504.1 WIND RESIS-
 TANCE OF ROOFS: ROOF DECKS AND ROOF
 COV-ERINGS SHALL BE DESIGNED FOR WIND
 LOADS IN ACCORDANCE WITH CHAPTER 16.
 PROVIDE
 PRODUCT TESTING REPORTS.
  
 13) 105.3(6) ADMINISTRATIVE CODE,
 SPECIAL INSPECTOR (RESIDENT INSPECTOR
 PROGRAM) REGISTER WITH OUTSIDE INSPEC-
 TION COORDINATOR DON NEELY 805-6665.
  
 14)FL BLD CODE 1804.2.2 QUESTIONABLE
 SOILS, WHERE THE BEARING CAPACITY IS
 NOT DEFINETLY KNOWN OR IS IN QUESTION.
 SUPPLY SIGNED/ SEALED SOILS REPORT FROM
 ARDAMANFILE # 02/2199 10/31,2002,
 REQUIRING 3,000 PSF
  
 15) STATE STATUTE 553.895(2) MULTI-FAM-
 ILY RESIDENTIAL BUILDINGS WHETHER DESIGN
 ATED AS TOWNHOUSE,CONDOMINIMUMS, APART-
 MENT HOUSES, TENEMENTS,GARDEN APARTMENTS
 OR BY ANY OTHER NAME ARE TO BE FIRE
 SPRINKLERED. MISSING PLANS.903.8.2
  
 16)BEFORE A PERMIT TO CONSTRUCT, MAY
 BE ISSUED, IMPACT FEES MUST BE PAID TO
 PALM BEACH COUNTY. THE ACTUAL PERMIT
 SET OF PLANS MUST BE STAMPED BY THAT
 OFFICE, AND A COPY OF THE PAID RECEIPT
 ATTACHED TO THE PERMIT APPLICATION.
 PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 ********CLUBHOUSE*******
  
 17) SHEET AM-2, WOMENS RESTROOM HANDI-
 CAPPED STALL REQUIRES 18" PULL SIDE OF
 LATCH.
  
 18) AM-1 ROOF SHEATHING REQUIREMENTS:
 W.P.B. CITY AMENDMENTS TABLE 2306.1
 ROOF COVERING 1509: INSULATION, CORRECT
  
 19) AM-4 MAILBOXES, REACH RANGES,
 FAIR HOUSING, ANSI A117.1
 308.2.1 FORWARD REACH RANGES UNOBSTRUCT-
 ED 15"/48"
 308.3.1 SIDE REACH RANGES UNOBSTRUCTED
 15"/48"
  
 20) AM-4 MAIL BOX DETAIL, 2X4 WOOD FRAME
 WALL DETAIL, FRAMING C/C?
  
 21) AM-4 MAIL BOX DETAIL HI-RIB LATH
 CEILING ATTACHMENT/ SPACING? SEE ASTM
 C-1063.
  
 22)AM-2, AM-5 WINDOW SCHEDULE, LEASING
 OFFICE, CLOSING OFFICE, UNIT# 6 FIXED
 WINDOWS SEE 2405.2.1(3) GLAZING IN HAZ-
 ARDOUS LOCATIONS.
  
 23) CHECK WALL PRESSURES, WINDOW #3,
 INTERIOR & END ZONES, OVERHEAD DOOR?
  
 24) 13-400.1 ENERGY CODE SEE AM-7 CLUB-
 HOUSE DETAIL # 2. EXTERIOR BLOCK WALL,
 MEET THE MINIMUM INSULATION REQUIREMENTS
 FOR EXTERIOR BLOCK WALL "R-7" GENERAL
 BUILDINGS < 5,000 SQ FT (PRESCRIPTIVE
 REQUIREMENT)
  
 25) AM-7 CLUBHOUSE TRUSS ANCHOR SCHEDULE
 INDICATES USE OF NU-VUE PRODUCTS WITH
 LISTED LOADS, NOTE ON RIGHT SIDE OF PAGE
 INDICATES USE OF USP PRODUCTS OR EQUAL,
 1707.3.1 JOIST HANGERS, FRAMING
 ANCHORS & SIMILAR DEVICES SHALL BE TEST-
 ED IN ACCORDANCE W/ ASTM D 1761 & BE
 LABELED AND LISTED FOR THEIR LOAD CARRY-
 ING CAPACITY.
 IF OTHER PRODUCTS ARE USED, LIST THEIR
 LOAD CARRYING CAPACITY.
  
 26) AM-8 DETAILS 8 & 13, 2X4 BLOCKING
 DRAWN IN BLOCK, NOT ATTACHED TO THE CMU.
  
 ****APPARTMENT BUILDING COMMENTS*****
  
 27) 1014.1.1 STAIRS DO NOT MEET THE
 REQUIREMENT OF AN OPEN STAIRWAY. AT
 LEAST 50% OF THE BALCONY, PORCH,GALLERY
 OR SIMILAR SPACE SHALL BE OPEN ON THE
 LONG SIDE.
 THE EXCEPTION TAKEN FOR ARRANGEMENT
 & NUMBER OF EXITS 1004.1.4(3) WHEN YOU
 READ THE CODE ARTICLE THIS DEALS WITH
 SMOKE ISSUES IN A ENCLOSED EXIT ACCESS
 CORRIDOR. NOTE THE CODE ARTICLE DOES NOT
 DESCRIBE CONDITIONS DESCIBED UNDER
 1006.2 DEALING WITH EXTERIOR EXITWAY
 STAIRS.
 TWO ISSUES NEED TO BE ADDRESSED:
 A) 1004.1.4 IF THIS IS GOING TO BE CONS
 IDERED AN INTERIOR STIARWAY WITH THE
 EXCEPTION TAKEN IN 1004.1.4(3) VS 1/2
 THE DIAGONAL. IF 1004.1.4(2) THIS EXCEP-
 TION IS TAKEN, THEN 903.2 KICKS IN.
 AUTOMATIC SPRINKLER SYSTEMS INSTALLED IN
 LIEU OF OR, AS AN ALTERNATE TO OTHER
 REQUIREMENTS, AS PERMITTED BY THIS CODE
 SHALL BE CONSIDERED REQUIRED SYSTEMS AND
 SHALL COMPLY WITH NFPA 13 NOT 13R.
 B) THE SECOND ISSUE WILL BE THE OPEN
 STAIRWAY VS CLOSED.IF THE OWNERS APPLIES
 FOR A VARIANCE FOR THIS TO BE CONSIDERED
 A OPEN STAIRWAY:
 THE ISSUE OF 1/2 THE DIAGONAL VS 1/3 THE
 DIAGONAL WILL ALSO REQUIRE A NFPA 13
 SYSTEM. 1006.2.4 WILL ALSO BE AN ISSUE
 REQUIRING OPENING PROTECTIVES WITHIN 10
 FEET OF THE STAIRWAY, 3/4 HR RATING.
  
 28)905.2.1 RESIENTIAL SMOKE ALARMS:
 NFPA 72.A-8-1.2.1(B) ALL SMOKE DETECTORS
 SPECIFIED IN A-8-1.2.1(A) FOR EXISTING
 CONSTRUCTION ARE REQUIRED, AND, IN ADD-
 TION, A SMOKE DETECTOR IS REQUIRED IN
 EACH SLEEPING ROOM.
 ELEC. PLAN DO NOT INDICATE SMOKE DE-
 TECTORS IN THE HALLWAYS ADJACENT TO
 SLEEPING ROOMS.
  
 29) SHEET S-D1 DETAIL"A" STEEL COLUMN
 DOESN'T GIVE WELD SIZES.
  
 30) 1804.1.3 THE BOTTOM OF THE FOUNDA-
 TION SHALL EXTEND NO LESS THAN 12"
 BELOW FINISH GRADE. 1909.1 MINIMUM SLAB
 THICKNESS SLAB ON GRADE 31/2".SHEET S-D5
 THE FOUNDATION SCHEDULE HAS FOUNDATION
 DEPTHS OF 12" NOT THE 15 1/2" REQUIRED
 BY CODE. THE OTHER ISSUE IS THE ARCH
 SHEET A-DT5 DETAIL "N" THE SLAB IS ONLY
 8" BENEATH THE GRADE. ALSO SEE 1403.1.6
  
 LOOK FOR COMMENTS BY THE OTHER PLAN
 REVIEW DISCIPLINES THAT MAY BE WRITTEN
 ON THE APPLICATION, PLANS, OR ATTACHED
 SEPARATELY. WHEN RESUBMITTING PLANS
 PLEASE CLEARLY INDICATE THE REVISION AND
 REMOVE AND REPLACE ANY PAGES AS NECESS-
 ARY. SUBMIT (1) SET OF OLD DRAWINGS WITH
 THE PLANS WHEN RESUBMITTING PLANS. A
 TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR
 SPECIFICATION PAGE WHERE THE CHANGES CAN
 BE FOUND, WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
 JIM WITMER
 BUILDING PLAN REVIEW
 TEL: (561)805-6715
 FAX: (561)659-8026