| 2003-06-30 00:00:00 | BUILDING PLAN REVIEW |
| | *******DENIED******* |
| | ROBERT BROWN(561) 805 6716 |
| | E-MAIL: [email protected] |
| | |
| | FBC = FLORIDA BUILDING CODE 2001 |
| | FBC*= FLORIDA BUILD'G CODE (CITY AMEND) |
| | |
| | FOR CONSISTENCY, THE FOLLOWING COMMENTS |
| | ARE NUMBERED AS PER THE BUILDING PLAN |
| | REVIEW OF 6/20/03: |
| | |
| | 2) THIS COMMENT HAS NOT BEEN PROPERLY |
| | ADDRESSED.THE SUBMITTED COPIES OF ARCH |
| | ALUMINUM DOOR PRODUCT APPROVAL NOA# |
| | 01.0910.09 ARE BETTER QUALITY BUT THERE |
| | IS A BLANK STRIP ACROSS EACH OF THE |
| | DRAWING SHEETS.THIS BLANK STRIP |
| | RENDERS THE MIAMI-DADE PRODUCT CONTROL |
| | STAMPS AND THE ANCHOR FASTENER SCHEDULE |
| | (SHEET 4 OF 4) ILLEGIBLE. SUBMIT LEGIBLE |
| | COPIES. |
| | |
| | 3) THIS COMMENT HAS NOT BEEN ADDRESSED. |
| | FBC 1606.1.7WIND LOAD.THE PLANS |
| | SHALL STATE THE BASIC WIND SPEED, WIND |
| | IMPORTANCE FACTOR, WIND EXPOSURE |
| | CATEGORY, INTERNAL PRESSURE COEFFICIENT, |
| | AND EXTERIOR COMPONENT AND CLADDING |
| | DESIGN WIND PRESSURES SO THAT THEY CAN |
| | BE COMPARED TO THE ALLOWABLE PRESSURES |
| | ON THE PRODUCT APPROVAL. |
| | |
| | **QUOTE PERMIT# ON ALL CORRESPONDENCE** |
| | |
| | END OF REVIEW COMMENTS |
| | THE CODE REFERENCES GIVE ADDITIONAL INFO |
| | TELEPHONE: (561) 805 6716ROBERT BROWN |
| | E-MAIL: [email protected] |