2003-06-20 00:00:00BUILDING PLAN REVIEW
 *******DENIED*******
 ROBERT BROWN(561) 805 6716
 E-MAIL: [email protected]
  
 FBC = FLORIDA BUILDING CODE 2001
 FBC*= FLORIDA BUILD'G CODE (CITY AMEND)
  
 1) HURRICANE MISSILE IMPACT PROTECTION
 SHUTTERS.THE SUBMITTED ARCH ALUMINUM
 DOOR PRODUCT APPROVAL NOA# 01-0910.09
 REQUIRES THE INSTALLATION OF HURRICANE
 PROTECTION FOR THIS DOOR.SUBMIT A
 PRODUCT APPROVAL FOR SHUTTERS AND
 ANNOTATE ON THE PLANS.
  
 2) THE SUBMITTED COPIES OF ARCH ALUMINUM
 DOOR PRODUCT APPROVAL NOA# 01.0910.09
 ARE OF POOR QUALITY.THE INFORMATION,
 INCLUDING THE FASTENER SCHEDULE (SHEET 4
 OF 4) IS NOT LEGIBLE.SUBMIT LEGIBLE
 COPIES.MIAMI-DADE PRODUCT APPROVALS
 CAN BE PRINTED FROM THEIR WEBSITE,WWW.
 MIAMIDADE.GOV/BUILDINGCODE/PC-SEARCH.HTM
  
 3) FBC 1606.1.7WIND LOAD.THE PLANS
 SHALL STATE THE BASIC WIND SPEED, WIND
 IMPORTANCE FACTOR, WIND EXPOSURE
 CATEGORY, INTERNAL PRESSURE COEFFICIENT,
 AND EXTERIOR COMPONENT AND CLADDING
 DESIGN WIND PRESSURES SO THAT THEY CAN
 BE COMPARED TO THE PRODUCT APPROVAL.
  
 **QUOTE PERMIT# ON ALL CORRESPONDENCE**
  
 END OF REVIEW COMMENTS
 THE CODE REFERENCES GIVE ADDITIONAL INFO