| Notes |
| Date |
Text |
| 2003-05-23 00:00:00 | UNSAT | | | ~~~~~ | | | ~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~ | | | PLEASE MAKE THE FOLLOWING CHANGES TO | | | THE PLANS FOR CODE COMPLIANCE AND | | | RESUBMIT FOR REVIEW. | | | | | | 1} THE RISER DIAGRAM INDICATES A 150 AMP | | | PANEL WITH A 200AMP "DISCONNECT", | | | PLEASE CORRELATE. | | | | | | 2} THE 1/0 CONDUCTORS ARE INCORRECT FOR | | | A 200 AMP OCP.FROM THE METER TO THE | | | PANEL. | | | | | | 3} THE 50 AMP OCP.IS NOT CORRECT FOR A | | | 10000 W AHU @ 125% | | | | | | 4} PLEASE LIST THE REQ,D BATH(S) | | | CIRCUIT(S). PER 210-11-C-3 | | | MUST BE 20A AND #12AWG."SHALL HAVE NO | | | OTHER OUTLETS". | | | | | | 5} THERE MUST BE SMOKE DETECTORS SHOWN | | | ON THE PLAN TO COMPLY WITH NFPA-72 | | | 8-1.4.1.6 | | | | | | 6} PLEASE GIVE ROOM DESIGNATIONS ON | | | ELECRICAL PLAN. | | | | | | 7} RECEPTACLES ARE MISSING FROM THE | | | MASTER BATH. COMPLY WITH 210-52(D). | | | | | | 8} BATH #3 NOT IN COMPLIANCE WITH | | | 210-52(D). | | | | | | 9} THE MASTER BEDROOM &,BEDROOM #2,THE | | | GUEST BEDROOM AND THE DINNING ROOM ALL | | | NEED RECEPTACLES ADDED TO COMPLY WITH | | | 210-52(A)(1). | | | | | | IF THERE ARE ANY QUESTIONS PLEASE CALL. | | | | | | BILL TROBAUGH | | | ELECTRICAL PLAN REVIEW | | | 561/805-6718 |
|