Plan Review Notes
Plan Review Notes For Permit 03051173
Permit Number 03051173
Review Stop E
Sequence Number 1
Notes
Date Text
2003-05-23 00:00:00UNSAT
 ~~~~~
 ~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~
 PLEASE MAKE THE FOLLOWING CHANGES TO
 THE PLANS FOR CODE COMPLIANCE AND
 RESUBMIT FOR REVIEW.
  
 1} THE RISER DIAGRAM INDICATES A 150 AMP
 PANEL WITH A 200AMP "DISCONNECT",
 PLEASE CORRELATE.
  
 2} THE 1/0 CONDUCTORS ARE INCORRECT FOR
 A 200 AMP OCP.FROM THE METER TO THE
 PANEL.
  
 3} THE 50 AMP OCP.IS NOT CORRECT FOR A
 10000 W AHU @ 125%
  
 4} PLEASE LIST THE REQ,D BATH(S)
 CIRCUIT(S). PER 210-11-C-3
 MUST BE 20A AND #12AWG."SHALL HAVE NO
 OTHER OUTLETS".
  
 5} THERE MUST BE SMOKE DETECTORS SHOWN
 ON THE PLAN TO COMPLY WITH NFPA-72
 8-1.4.1.6
  
 6} PLEASE GIVE ROOM DESIGNATIONS ON
 ELECRICAL PLAN.
  
 7} RECEPTACLES ARE MISSING FROM THE
 MASTER BATH. COMPLY WITH 210-52(D).
  
 8} BATH #3 NOT IN COMPLIANCE WITH
 210-52(D).
  
 9} THE MASTER BEDROOM &,BEDROOM #2,THE
 GUEST BEDROOM AND THE DINNING ROOM ALL
 NEED RECEPTACLES ADDED TO COMPLY WITH
 210-52(A)(1).
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/805-6718