2003-06-18 00:00:00BUILDING PLAN REVIEW
 PERMIT: 03051173
 ADD: 10214 SAND CAY LANE
 CONT: G W PURUCKER HOMES
 TEL: (561)775-1170
 FL BLD CODE= 2001 FLORIDA BUILDING CODE
  
 ACTION: DENIED
  
 NOTE: FUTURE POOL,
 1803.1.3 EXCAVATION FOR ANY PURPOSE
 SHALL NOT EXTEND WITHIN 1 FT OF THE
 ANGLE OF REPOSE OR NARURAL SLOPE OF THE
 SOIL UNDER ANY FOOTING OR FOUNDATION,
 UNLESS SUCH FOOTING OR FOUNDATION IS
 FIRST PROPERLY UNDERPINNED OR PROTECTED
 AGAINST SETTLEMENT. COVERED LOGGIA ,
 COLUMN FOOTING MAY REQUIRE UNDERPINNING.
  
  
 1) 61G15-23.002(2) IF AN ENGINEER SIGNS
 AND SEALS PLANS A TITLE BLOCK ON EACH
 SHEET CONTAINING THE PRINTED NAME,
 ADDRESS, AND NUMBER OF THE ENGINEER OR
 BUSINESS WILL SATISFY THIS REQUIRMENT.]
  
 2)FL BLD CODE 104.2.1.2
 ADDITIONAL INFORMATION REQUIRED,
 A) ZERO LOT LINE, A/C COMPRESSOR ON LOT
 (11).
 B)PROVIDE DOCUMENTATION FOR AN EASEMENT
 (EMERGENCY ACCESS) FOR BEDROOM# 2.
  
 3)905.2.1 APPROVED SINGLE-STATION OR
 MULTIPLE STATION SMOKE DETECTORS SHALL
 BE INSTALLED IN ACCORDANCE WITH NFPA 72,
 CHAPTER 2, WITHIN EVERY DWELLING UNIT
 WITHIN AN APARTMENT HOUSE, CONDOMINIMUM,
 OR TOWNHOUSE AND EVERY GUEST OR SLEEPING
 ROOM IN A MOTEL, HOTEL, OR DORMITORY &
 SLEEPING ROOMS IN RESIDENTIAL CARE/
 ASSISTED LIVING OCCUPANCIES. WHERE MORE
 THAN ONE DETECTOR IS REQUIRED TO BE
 INSTALLED WITHIN INDIVIDUAL DWELLING
 UNIT, THE DETECTOR SHALL BE WIRED IN
 SUCH A MANNER THAT THE ACTUATION OF ONE
 ALARM WILL ACTIVATE ALL THE ALARMS IN
 THE INDIVIDUAL UNIT. ALARMS SHALL ALSO
 BE MOUNTED ON THE HALL SIDE OF BEDROOMS
 EITHER WALL OR CEILING APPLICATION.
  
 4) MEAN ROOF HEIGHT: SHEET A_2.1, SHOULD
 BE TAKEN FROM HEIGHEST BEAM THEN 1/2 THE
 ROOF HEIGHT, 12'+5'-3"= 17'-3".
  
 5) SHEET A-4 BUCK DETAIL:
 1707.4.4.2 TAPERED BUCKS:
 SHALL EXTEND BEYOND THE INTERIOR FACE
 OF THE WINDOW OR DOOR FRAME SUCH THAT
 FULL SUPPORT OF THE FRAME IS SUPPORTED.
  
 6) SHEET A-7 AIR HANDLER LIVE LOAD,
 ATTIC STORAGE IN GARAGE, FINK TRUSS (T2)
 INDICATES 0 LBS LIVE LOAD ON BOTTOM
 TRUSS CHORD.T1604.1 30 LBS ATTIC STORAGE
  
 7) DESIGN PROFESSIONAL TO REVIEW &
 APPROVE, APPROVE WITH COMMENTS BEFORE
 TRUSS ENGINEERING IS SUBMITTED TO THE
 BUILDING DEPARTMENT.
  
 8) SHEET A-5, ATTACHMENT SCHEDULE
 A) THE ATTACHMENT FOR FLAT TILE AND
 BARREL TILE TO MATCH PRODUCT TESTING RE-
 PORTS. CALCULATIONS FOR ROOF ZONES 1,2
 & 3 SUBMITTED WHAT TYPE OF FASTENING
 SYSTEM WILL BE USED?
  
 BARREL TILE INDICATES THE USE OF BOX
 NAILS OR (SINKERS) WHAT IS THE VALUE FOR
 THIS NAIL?
  
 WIRE LATH SOFFITS: THIS DOES NOT INDI-
 CATE IF THE METAL LATH WILL BE FLAT OR
 RIBBED LATH, HIRIBBED LATH IS TO BE FAST
 ENED TO HORIZONTAL FRAMING MEMBERS WITH
 1 3/4" PENETRATION INTO THE FRAMING MEM-
 BER @ 4" O.C. (EACH RIB)
 ASTM C-1063.7.10.1.1
  
 WIRE LATH WALLS: THIS SAME SECTION
 ASTM C-1063.7.10.1.1. FLAT WIRE LATH
 SHALL BE NAILED @ 7" O.C. WITH THE NAIL
 CLEATED OVER TO ENGAGE 3 STRANDS.
  
 9) SHUTTER INSTALLATION SCHEDULE, INDI-
 CATES THE USE OF CALK-INS @ 12" O.C.
 THE CONTRACTOR IS TAKING THE VALUE FOR
 3000PSI CONCRETE. EITHER THE CONTRACTOR
 CHANGE THE INSTALLATION SCHEDULE TO RE-
 FLECT THE VALUE FOR MASONARY BLOCK,
 ANCHORS @ 7" O.C. OR SUBMIT A NOTIRIZE
 AFFADAVIT STATING THE CALK-INS TO BE A
 MINIMUM OF 2 3/4" TO ASSURE THE VALUES
 FOR 3000 PSI CONCRETE.
  
 LOOK FOR COMMENTS BY THE OTHER PLAN
 REVIEW DISCIPLINES THAT MAY BE WRITTEN
 ON THE APPLICATION, PLANS, OR ATTACHED
 SEPARATELY. WHEN RESUBMITTING PLANS
 PLEASE CLEARLY INDICATE THE REVISION AND
 REMOVE AND REPLACE ANY PAGES AS NECESS-
 ARY. SUBMIT (1) SET OF OLD DRAWINGS WITH
 THE PLANS WHEN RESUBMITTING PLANS. A
 TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR
 SPECIFICATION PAGE WHERE THE CHANGES CAN
 BE FOUND, WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
 JIM WITMER
 BUILDING PLAN REVIEW
 TEL: (561)659-8096 X 8412
 FAX: (561)659-8026