| 2003-10-07 00:00:00 | *********** UNSAT******** |
| | |
| | PLEASE SEE THAT PLANS MUST BE REVISED |
| | AND RESUBMITTED. PLEASE CALL TO SET UP |
| | TIME TO GO OVER PLANS BEFORE RESUBMITT- |
| | -ING. |
| | 1)NOTE: PLEASE SEE RECEPT SPACING ALONG |
| | KITCHEN COUNTERSPACE PERE 210.52C1 |
| | |
| | 2)NOTE: PLEASE CORRECT SIZING OF |
| | CONDUCTORS ON PANEL SCHEDULE W/ OCP. |
| | 20A SHOWN W/ #14'S ETC. |
| | PLEASE SEE THAT ALL OTHER CONDUCTORS ARE |
| | MISSING. |
| | |
| | 3)NOTE: PLEASE SEE 424.3, SHOWS AHU AS |
| | 10KW AND YET PANEL SCHEDULE SHOWS A |
| | 20A-1P FEED??? |
| | |
| | 4)NOTE: PLEASE SEE RISER DIAGRAM, SHOWS |
| | A #8 EQUIPMENT GROUNDING CONDUCTOR TO |
| | PANEL. BOTH MAIN AND PANEL ARE SHOWN TO |
| | BE 150A.PLEASE SEE 250.122 AS NOTED ON |
| | RISER, #8 SHOWN IS ONLY RATED UP TO |
| | 100A'S. PLEASE ADJUST. |
| | |
| | 5)NOTE: PLEASE CORRELATE RISER & PLANS, |
| | RISER SHOWS SERVICE AS EXISTING 150A AND |
| | PLAN SHOWS AS EXISTING 200A?? |
| | |
| | 6)NOTE: PLEASE SEE COPY OF FS 553.80(2), |
| | (B) WITH RESPECT TO DESIGN PROFESSIONALS |
| | |
| | 7)NOTE: PLEASE SEE SD REQD IN MASTER |
| | BEDROOM SITTING RM.NFPA-72 |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. IF THERE ARE ANY QUESTIONS, |
| | PLEASE CALL. |
| | |