| 2003-06-20 00:00:00 | ************* UNSAT ************** |
| | |
| | PLANS/RISER IS SHOWN DIFFERENT FROM |
| | FIRST REVIEW AND NOW HAVE OTHER COMMENTS |
| | |
| | 1)NOTE: PLEASE SEE THAT NEW PANEL IS |
| | SHOWN BEING FED FROM METER WITH A NEW |
| | MAIN AND IS NOT FED FROM EXISTING 200A |
| | PANEL. |
| | MAINS ARE TO BE GROUPED PER 230-72. NEC |
| | |
| | 2)NOTE: PLEASE INCLUDE CONDUIT AND WIRE |
| | SIZES FOR UPGRADE OF PANEL FROM 100A TO |
| | 150A. |
| | |
| | 3)NOTE: PLEASE SHOW SIZE OF EXISTING |
| | SERVICE ENTRANCE CONDUCTORS AND METER |
| | CAN. SERVICE IS NOW SIZED TO 350A`S |
| | AND NEEDS TO HAVE GROUNDING ELECTRODE |
| | SYSTEM UPGRADED. DUE TO INCREASE IN |
| | OVERALL SERVICE SIZE. PLEASE SIZE |
| | SEC`S TO 310-15 AND GROUNDING ELECTRODE |
| | CONDUCTOR TO 250-66. |
| | |
| | 4)NOTE: PLEASE PROVIDE AIC RATING FOR |
| | ANY NEW ELECTRICAL SERVICE EQUIPMENT. |
| | 110-9/215-5 |
| | |
| | 5)NOTE: PLEASE INCLUDE NEW BLDG FOOTER |
| | STEEL TO BE PART OF GROUNDING ELECTRODE |
| | 250-50 ALONG W/ EXISTING COLD WATER. |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW.DUE TO THE SERVICE CHANGING |
| | AGAIN, THERE MAY BE OTHER COMMENTS. |
| | PLEASE CALL TO GO OVER COMMENTS AND |
| | SET UP A TIME TO GO OVER PLANS OR |
| | SERVICE. |
| | |