2003-06-20 00:00:00************* UNSAT **************
  
 PLANS/RISER IS SHOWN DIFFERENT FROM
 FIRST REVIEW AND NOW HAVE OTHER COMMENTS
  
 1)NOTE: PLEASE SEE THAT NEW PANEL IS
 SHOWN BEING FED FROM METER WITH A NEW
 MAIN AND IS NOT FED FROM EXISTING 200A
 PANEL.
 MAINS ARE TO BE GROUPED PER 230-72. NEC
  
 2)NOTE: PLEASE INCLUDE CONDUIT AND WIRE
 SIZES FOR UPGRADE OF PANEL FROM 100A TO
 150A.
  
 3)NOTE: PLEASE SHOW SIZE OF EXISTING
 SERVICE ENTRANCE CONDUCTORS AND METER
 CAN. SERVICE IS NOW SIZED TO 350A`S
 AND NEEDS TO HAVE GROUNDING ELECTRODE
 SYSTEM UPGRADED. DUE TO INCREASE IN
 OVERALL SERVICE SIZE. PLEASE SIZE
 SEC`S TO 310-15 AND GROUNDING ELECTRODE
 CONDUCTOR TO 250-66.
  
 4)NOTE: PLEASE PROVIDE AIC RATING FOR
 ANY NEW ELECTRICAL SERVICE EQUIPMENT.
 110-9/215-5
  
 5)NOTE: PLEASE INCLUDE NEW BLDG FOOTER
 STEEL TO BE PART OF GROUNDING ELECTRODE
 250-50 ALONG W/ EXISTING COLD WATER.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW.DUE TO THE SERVICE CHANGING
 AGAIN, THERE MAY BE OTHER COMMENTS.
 PLEASE CALL TO GO OVER COMMENTS AND
 SET UP A TIME TO GO OVER PLANS OR
 SERVICE.
  