Plan Review Notes
Plan Review Notes For Permit 03051079
Permit Number 03051079
Review Stop E
Sequence Number 1
Notes
Date Text
2003-05-16 00:00:00*************** UNSAT ***********
  
 1)NOTE: PLEASE CORRELATE RISER DIAGRAM,
 PANELS, LOAD CALCS AND NOTES TO PLANS.
 NOTE SHOWS A NEW 150A SERVICE, RISER
 SHOWS EXISTING 200A SERVICE? AND SUB
 PANEL IS SHOWN AS EXIST 100A TO REMAIN
 AND 150A NEW??
 215-5
  
 2)NOTE: PLEASE LIST ARC FAULT CIRCUITS
 PER 210-12
  
 3)NOTE: PLEASE SHOW ALL OULETS SERVING
 KITCHEN COUNTERSPACE AS GFI/ GFI
 PROETCTED. 210-8-A-6
  
 4)NOTE: PLEASE SHOW RECEPT SPACING ALONG
 COUNTERSPACE PER 210-52C1
  
  
  
  
  
 6)NOTE: PLEASE PROVIDE LICENSE/ FIRM #
 REQ`D ON TITLE BLOCK PER FS/FAC
 61G1-16.004 FOR ARCH OF RECORD.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW.PLEASE TAKE OUT ALL OLD/VOIDED
 SHEETSAND INSERT NEW SHEETS INTO TWO
 COMPLETE SETS FOR REVIEW AND STAMPING.
  
 IF THERE ARE ANY QUESTIONS, PLEASE CALL.
  
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]