Plan Review Notes
Plan Review Notes For Permit 03051031
Permit Number 03051031
Review Stop P
Sequence Number 2
Notes
Date Text
2003-07-05 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 CHAPTER 11
  
 A) FROM PREVIOUS REVIEW
 1) IF THE OCCUPANCY CLASSIFICATION OR
 OCCUPANCY SUBCLASSIFICATION OF ANY
 BUILDING OR STRUCTURE IS CHANGED, THE
 BUILDING, ELECTRICAL, GAS, MECHANICAL, &
 PLUMBING SYSTEMS SHALL BE MADE TO CON-
 FORM TO THE INTENT OF THE TECHNICAL
 CODES AS REQUIRED BY THE BUILDING OFFI-
 CAL. SEC 3401.2.2.1 BLDG CODE
 20 11-4.1.1(6) IF BATHING FACILITIES ARE
 PROVIDED ON A SITE, THEN EACH SUCH PUB-
 LIC OR COMMON USE BATHING FACILITY SHALL
 COMPLY WITH SECTION 11-4.23 - BATHING
 ROOM DETAIL REQUIRED. SHOW CLEAR FLOOR
 SPACE, TURNING CIRCLE, HEIGHTS, GRAB-
 BARS, ECT. SHOW COMPLIANCE FOR ALL SECT-
 IONS AND SUBSECTIONS REQUIRED BY CODE.
 *** NEW COMMENTS ***
 3) IF A WATER COOLER IS USED, IS SHALL
 COMPLY WITH ARI-1010 AS PER SEC 410.4 &
 MANUF INFO. IS REQUIRED AT TIME OF FINAL
 PLUMBING INSPECTION.
 4) TURNING CIRCLE NOT SHOWN IN TOILET
 ROOM. PLEASE SHOW ON TOILET ROOM DETAIL.
 SECTION 11-4.22.3
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692