Plan Review Notes
Plan Review Notes For Permit 03051031
Permit Number 03051031
Review Stop B
Sequence Number 2
Notes
Date Text
2003-06-25 00:00:00BUILDING PLAN REVIEW
 *******DENIED*******
 ROBERT BROWN(561) 805 6716
 E-MAIL: [email protected]
  
 FBC = FLORIDA BUILDING CODE 2001
 FBC*= FLORIDA BUILD'G CODE (CITY AMEND)
  
 FOR CONSISTENCY, THE FOLLOWING COMMENTS
 ARE NUMBERED AS PER THE BUILDING PLAN
 REVIEW OF 6/5/03:
  
 3) 11-4.15WATER COOLER. NOTE 17 STATES
 THAT THE TENANT IS TO PROVIDE A WATER
 COOLER.THE PLANS SHALL BE AMENDED/
 ANNOTATED TO SPECIFY THE REQUIREMENTS
 FOR SPOUT HEIGHT/LOCATION AND FOR
 WHEELCHAIR APPROACH CLEARANCES (REF:
 FIG. 27).ANY PLUMBING PLAN REVIEW
 COMMENTS ON THE WATER COOLER OR DRINKING
 FOUNTAIN REQUIREMENTS SHALL BE ADDRESSED
  
 4) FBC 11-4.13.6MANEUVERING CLEARANCES
 AT DOORS. DOOR 3 SHALL HAVE AT LEAST 18"
 CLEARANCE BETWEEN THE LEADING EDGE OF
 THE DOOR AND THE ADJACENT OFFICE WALL ON
 THE PULL SIDE OF THE DOOR (REF: FIG. 25)
  
 5) THE PLAN HAS BEEN REDRAWN.THE NEW
 SHEETS SHALL BE REVIEWED AND STAMPED
 'APPROVED' BY THE CITY PLACE
 ADMINISTRATION.
  
 **QUOTE PERMIT# ON ALL CORRESPONDENCE**
  
 END OF REVIEW COMMENTS
 THE CODE REFERENCES GIVE ADDITIONAL INFO
 TELEPHONE: (561) 805 6716ROBERT BROWN
 E-MAIL: [email protected]