Plan Review Notes
Plan Review Notes For Permit 03051031
Permit Number 03051031
Review Stop P
Sequence Number 1
Notes
Date Text
2003-06-11 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 CHAPTER 11
 FBC-2001 BUILDING
  
 1) IF THE OCCUPANCY CLASSIFICATION OR
 OCCUPANCY SUBCLASSIFICATION OF ANY
 BUILDING OR STRUCTURE IS CHANGED, THE
 BUILDING, ELECTRICAL, GAS, MECHANICAL, &
 PLUMBING SYSTEMS SHALL BE MADE TO CON-
 FORM TO THE INTENT OF THE TECHNICAL
 CODES AS REQUIRED BY THE BUILDING OFFI-
 CAL.SEC 3401.2.2.1
 2) 11-4.1.1(6) IF TOILET FACILITIES ARE
 PROVIDED ON A SITE, THEN EACH SUCH PUB-
 LIC OR COMMON USE TOILET FICILITY SHALL
 COMPLY WITH 11-4.22. IF BATHING FACILIT-
 IES ARE PROVIDED ON A SITE, THEN EACH
 SUCH PUBLIC OR COMMON USE BATHING FACIL-
 ITY SHALL COMPLY WITH SECTION 11-4.23.
 SUBMIT DETAIL FOR BOTH THE TOILET ROOM
 AND THE BATHROOM. SHOW CLEAR FLOOR SPACE
 AND TURNING CIRCLE, HEIGHTS, GRAB BARS,
 ECT. SHOW DETAILS FOR ALL SUBSECTIONS.
 3) KITCHEN SINK SHALL CONFORM TO SECTION
 11-4.24 AND ALL SUBSECTIONS. SUBMIT DE-
 TAIL FOR SINK SHOWING COMPLIANCE WITH
 ALL SUBSECTIONS.
 4) TABLE 403.1 REQUIRES A DRINKING
 FOUNTAIN. (ALSO SEE SECTION 410.1)
 5) IF ANY CHANGES TO THE SANITARY PIPING
 OR WATER PIPING SYSTEMS, A SANITARY
 RISER DIAGRAM AND A WATER DIAGRAM SHALL
 BE REQUIRED. SEC 104.2.1
  
 REVIEW BY KEN STEVENS
 (561) 659-8096 EXT 8377
 (561) 805-6721
 FAX (561) 653-2692