| Notes |
| Date |
Text |
| 2003-05-19 00:00:00 | ************ UNSAT **************** | | | | | | 1)NOTE: PLANS NEED TO SHOW ALL CIRCUIT- | | | -ING AND CORRELATE W/ A SUBMITTED PANEL | | | SCHEDULE. 215-5. | | | | | | 2)NOTE: PLEASE SHOW CIRCUITING FOR EM/ | | | EXT LTS PER 700-12E | | | | | | 3)NOTE: PLEASE CLARIFY TWO OTHER NEW | | | OFFICE AREAS SHOWN W/ NO ELECTRICAL? | | | | | | 4)NOTE" PLEASE SHOW LOAD CALCUALTIONS, | | | PER 220-3,220-10,220-11,220-13 AND ALL | | | CONTINUOUS LOADS AT 125% 230-42/215-3 | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-805-6717 | | | [email protected] |
|