Plan Review Notes
Plan Review Notes For Permit 03051031
Permit Number 03051031
Review Stop E
Sequence Number 1
Notes
Date Text
2003-05-19 00:00:00************ UNSAT ****************
  
 1)NOTE: PLANS NEED TO SHOW ALL CIRCUIT-
 -ING AND CORRELATE W/ A SUBMITTED PANEL
 SCHEDULE. 215-5.
  
 2)NOTE: PLEASE SHOW CIRCUITING FOR EM/
 EXT LTS PER 700-12E
  
 3)NOTE: PLEASE CLARIFY TWO OTHER NEW
 OFFICE AREAS SHOWN W/ NO ELECTRICAL?
  
 4)NOTE" PLEASE SHOW LOAD CALCUALTIONS,
 PER 220-3,220-10,220-11,220-13 AND ALL
 CONTINUOUS LOADS AT 125% 230-42/215-3
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]