2003-06-05 00:00:00BUILDING PLAN REVIEW
 *******DENIED*******
 ROBERT BROWN(561) 805 6716
 E-MAIL: [email protected]
  
 FBC = FLORIDA BUILDING CODE 2001
 FBC*= FLORIDA BUILD'G CODE (CITY AMEND)
  
 1) FBC* 104.2.2THE SUBMITTED 'GENERAL
 NOTES' SHEET SHALL BE SIGNED, DATED AND
 SEALED BY THE DESIGN PROFESSIONAL OF
 RECORD.
  
 2) FBC 11-4.1.6(3)(E) ACCESSIBLE TOILET.
 THE PLAN DOES NOT STATE WHETHER THE
 EXISTING TOILET IS ACCESSIBLE, ADAPTABLE
 (PER FAIR HOUSING ACCESSIBILITY GUIDE,
 AS THIS IS A 'LIVE/WORK LOFT') OR
 NON-ACCESSIBLE.AMEND THE PLAN TO
 DEMONSTRATE COMPLIANCE WITH THE
 REQUIREMENT FOR AN ACCESSIBLE TOILET.
  
 3) FBC 11-4.1.3DRINKING FOUNTAIN.
 AMEND THE PLANS TO SHOW THE PROVISION OF
 AN ACCESSIBLE DRINKING FOUNTAIN WITH
 HEIGHT AND CLEARANCES IN COMPLIANCE WITH
 FIG 27.
  
 **QUOTE PERMIT# ON ALL CORRESPONDENCE**
  
 END OF REVIEW COMMENTS
 THE CODE REFERENCES GIVE ADDITIONAL INFO
 TELEPHONE: (561) 805 6716ROBERT BROWN
 E-MAIL: [email protected]