| Plan Review Notes For Permit 03050964 |
| Permit Number |
03050964 |
|
| Review Stop |
FIRE |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2004-01-12 00:00:00 | ***************DENIED******************* | | | 1) INTERIOR FINISH FOR WALL AND CEILING | | | ARE REQUIRED TO BE CLASS "A" OR CLASS "B | | | | | | 2) THE REAR EXIT DOORS SHOULD SWING OUT | | | (TENANT SPACE ON THE END THAT HAVE | | | DOUBLE DOORS) | | | | | | 3) THE DOOR TO THE RESTROOM IN SAME | | | SPACE BLOCKS ACCESS TO REAR EXIT DOORS | | | WHEN IN THE OPEN POSITION. | | | | | | 4) BUILDING ADDRESSES ARE REQUIRED. | | | COULD NOT LOCATE THEM ON ELEVATION | | | DRAWINGS. | | | | | | NATE MCCRAY, CAPTAIN | | | 805-6722 OR 835-2910 |
|