| Plan Review Notes For Permit 03050917 |
| Permit Number |
03050917 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2003-05-19 00:00:00 | **************FAILED************* | | | 1.WINDOW REPLACEMENT MUST MEET FBC2001, | | | 2. IF WINDOWS ARE NOT IMPACT WINDOWS | | | THEY MUST BE PROTECTED WITH STORM | | | PANELS. PER FBC2001 | | | 3. IF 2 WINDOWS ARE MULLED TOGETHER THE | | | PRODUCT APPROVALS FOR MULLS MUST BE | | | SUBMITTED. | | | 4. STORM PANEL PRODUCT APPROVALS MUST BE | | | SUBMITTED TO BE ADDED TO THIS PERMIT. | | | 5. BEDROOMS REQUIRE AT LEAST ONE WINDOW | | | TO MEET THE MEANS OF EGRESS PER FBC2001 | | | SEC. 1005.4.4(24" HI & 20" WIDE) | | | | | | | | | ANY QUESTIONS PLEASE CALL: | | | LEA SMITH, BUILDING PLANS EXAMINER | | | 805-6713 |
|