| Plan Review Notes For Permit 03050855 |
| Permit Number |
03050855 |
|
| Review Stop |
E |
| Sequence Number |
3 |
|
| Notes |
| Date |
Text |
| 2004-04-27 00:00:00 | ****** UNSAT ********* | | | | | | 1)NOTE: PLEASE CORRELATE PANEL SCHEDULES | | | /RISER DIAGRAM. | | | PANEL SHOWS EACH PANEL TO BE 200A SERV- | | | -ICE. MAIN BRKRS HAVE NOW BEEN CHANGED | | | TO 200A INSTEAD OF 150A AS SHOWN BEFORE. | | | PLEASE SEE CONDUCTORS UNDER NOTE ON | | | PANEL SCHEDULE. STILL SHOWS #1 FOR FEED- | | | -ERS??310.16 | | | PLEASE SEE NOW SERVICE HAS BEEN CHANGED | | | TO READ 400A. PLEASE SIZE GEC TO 250.66, | | | PER 310.15B6 | | | PLEASE SEE METERMAIN STILL ONLY INDICATE | | | -S 2-200A MCB'S? WHERE IS BRKR, (60A)? | | | FOR SUB PANEL??? | | | | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE DO NOT HESITATE TO CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | CITY OF WEST PALM BEACH | | | CONSTUCTION SERVICES DEPT. | | | 561-805-6717 | | | [email protected] |
|