| Plan Review Notes For Permit 03050855 |
| Permit Number |
03050855 |
|
| Review Stop |
B |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2003-08-11 00:00:00 | BUILDING PROVISO | | | | | | 1) SUBMIT A REVISED TRUSS ANCHOR | | | SCHEDULE WITH VALUES THAT DO NOT HAVE | | | A ONE-THIRD INCEASE ON THE STEEL | | | CALCULATIONS PER FBC 1609.4. SEE THE | | | 2003 USP CATALOG AND THE 2002 SIMPSON | | | HIGH WIND-RESISTANT CONSTRUCTION | | | CATALOG FOR THE PROPER VALUES. | | | | | | 2) THE TRUSS DRAWINGS AND LAYOUT FOR | | | SINGLE FAMILY DWELLINGS ARE NOT REQUIRED | | | TO BE SUBMITTED FOR PLAN REVIEW. THEY | | | ARE REQUIRED TO BE GIVEN TO THE FIELD | | | INSPECTOR AT THE ROOF FRAMING INSPECTION | | | NOTE: THE DRAWINGS DO NOT HAVE THE | | | ORIGINAL WET SIGNATURE OF THE TRUSS | | | ENGINEER ON THEM AND THE DRAWINGS HAVE | | | DIFFERENT MEAN ROOF HEIGHTS LISTED ON | | | THEM. |
|