| Plan Review Notes For Permit 03050853 |
| Permit Number |
03050853 |
|
| Review Stop |
B |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2003-08-12 00:00:00 | BUILDING PROVISO | | | | | | 1) TRUSS CONNECTOR SCHEDULE CONTAINS | | | SOME ERRORS. SUBMIT REVISED SCHEDULE. | | | SEE 2003 USP CATALOG AND 2002 SIMPSON | | | HIGH WIND-RESISTANT CONSTRUCTION CATALOG | | | | | | 2) SUBMIT PRODUCT APPROVALS FOR THE | | | FIXED ARCHED TOP (TOMBSTONE) FIXED GLASS | | | WINDOWS. | | | | | | 3) THE TRUSS DRAWINGS AND LAYOUT ARE NOT | | | REQUIRED TO BE SUBMITTED FOR PLAN | | | REVIEW. THEY ARE TO BE GIVEN TO THE | | | INSPECTOR AT THE ROOF FRAMING INSPECTION | | | NOTE: THE TRUSS DRAWINGS ARE REQUIRED TO | | | HAVE THE ORIGINAL WET SIGNATURE OF THE | | | TRUSS ENGINEER. THE MEAN ROOF HEIGHT IS | | | INCORRECT ON THE DRAWINGS(PLANS SPECIFY | | | 16'-9"MEAN ROOF HEIGHT). |
|