Plan Review Notes
Plan Review Notes For Permit 03050853
Permit Number 03050853
Review Stop B
Sequence Number 2
Notes
Date Text
2003-08-12 00:00:00BUILDING PROVISO
  
 1) TRUSS CONNECTOR SCHEDULE CONTAINS
 SOME ERRORS. SUBMIT REVISED SCHEDULE.
 SEE 2003 USP CATALOG AND 2002 SIMPSON
 HIGH WIND-RESISTANT CONSTRUCTION CATALOG
  
 2) SUBMIT PRODUCT APPROVALS FOR THE
 FIXED ARCHED TOP (TOMBSTONE) FIXED GLASS
 WINDOWS.
  
 3) THE TRUSS DRAWINGS AND LAYOUT ARE NOT
 REQUIRED TO BE SUBMITTED FOR PLAN
 REVIEW. THEY ARE TO BE GIVEN TO THE
 INSPECTOR AT THE ROOF FRAMING INSPECTION
 NOTE: THE TRUSS DRAWINGS ARE REQUIRED TO
 HAVE THE ORIGINAL WET SIGNATURE OF THE
 TRUSS ENGINEER. THE MEAN ROOF HEIGHT IS
 INCORRECT ON THE DRAWINGS(PLANS SPECIFY
 16'-9"MEAN ROOF HEIGHT).