| Date |
Text |
| 2003-06-25 00:00:00 | BUILDING DENIED |
| | |
| | 1) IMPACT FEES MUST BE PAID TO PALM |
| | BEACH COUNTY, PLANS STAMPED BY THEM AND |
| | COPY OF RECEIPT SUBMITTED TO CITY OF |
| | WEST PALM BEACH BUILDING DEPARTMENT, |
| | BEFORE A BUILDING PERMIT CAN BE ISSUED. |
| | |
| | 2) A RECORDED COPY OF THE NOTICE OF |
| | COMMENCEMENT MUST BE SUBMITTED BEFORE A |
| | PERMIT CAN BE ISSUED. |
| | |
| | 3) GLASS BLOCK ON THE ZERO LOT LINE IS |
| | REQUIRED TO BE ONE HOUR FIRE RATED. |
| | SPECIFY THIS ON THE FLOOR PLAN AND |
| | SUBMIT THE MANUFACTURE'S SPECIFICATIONS |
| | AND LISTING INFORMATION FOR THE ONE HOUR |
| | RATED GLASS BLOCK. |
| | |
| | 4) SUBMIT ENGINEERED DRAWINGS, SPECIFICA |
| | TIONS, ETC. FOR BUTT GLAZING AS REQUIRED |
| | BY FBC 2406.2. |
| | |
| | 5) WINDOWS WITHIN (3) FEET HORIZONTALLY |
| | OF A TUB OR A SHOWER ARE REQUIRED TO BE |
| | SAFETY GLAZING PER FBC 2405.2(2). PLEASE |
| | SPECIFY ON THE FLOOR PLAN. |
| | |
| | 6) THE FIXED GLASS WINDOWS IN THE GRAND |
| | ROOM ARE REQUIRED TO BE SAFETY GLAZING |
| | PER FBC 2405.2(4). PLEASE SPECIFY ON THE |
| | FLOOR PLAN. |
| | |
| | 7) ASTM C 926 REQUIRES STUCCO ON METAL |
| | LATH OVER A SOLID BASE TO BE 7/8". |
| | PLEASE REVISE WINDOW JAMB DETAIL AT |
| | FRAME WALL ON SHEET 5 AND DETAIL C ON |
| | SHEET 6A. |
| | |
| | 8) FBC 1609.4 DOES NOT ALLOW THE ONE- |
| | THIRD INCREASE ON THE STEEL CALCULATIONS |
| | FOR TRUSS ANCHORS. PLEASE REVISE THE |
| | VALUES IN THE ANCHOR SCHEDULE ON SHEET |
| | 3A. SEE 2003 USP OR 2002 SIMPSON HIGH |
| | WIND EDITION CATALOGS. HETAL16 WITH 5- |
| | 10D X 1-1/2" NAILS HAS UPLIFT OF 1365#, |
| | NOT 1383#. THERE ARE OTHER DISCREPACIES |
| | WITH LISTED VALUES. |
| | |
| | 9) TRUSS DRAWINGS ARE NOT REQUIRED TO BE |
| | SUBMITTED FOR PLAN REVIEW. THE ARE |
| | REQUIRED TO BE SUBMITTED TO THE BUILDING |
| | INSPECTOR IN THE FIELD AT THE ROOF |
| | FRAMING INSPECTION. |
| | |
| | 10) SUBMIT KEY PLAN AND INSTALLATION |
| | SCHEDULE FOR STORM PANELS. SPECIFY THE |
| | ANCHOR TYPE AND SPACING. CLARIFY THE |
| | TYPES OF MOUNTING BRACKETS (HEADERS,STUD |
| | ANGLE, ETC.) THAT WILL BE USED AT THE |
| | TOP AND BOTTOM OF THE PANELS. SAMPLE OF |
| | INSTALLATION SCHEDULE IS ATTACHED. |
| | |
| | 11) THE MULLION CALCULATIONS FOR WINDOWS |
| | 26A AND 16A DO NOT APPEAR TO BE CORRECT. |
| | PLEASE PROVIDE CLARIFICATION ON HOW THE |
| | INFORMATION USED TO ENTER THE TABLE WAS |
| | CALCULATED. (TRIBUTARY WIDTH AND MULLION |
| | SPAN) |
| | |
| | 12) PROVIDE (2) CURRENT AND COMPLETE |
| | COPIES OF SBCCI OR METRO-DADE PRODUCT |
| | APPROVALS FOR: |
| | - UNCLIPPED MULLIONS (EXPIRED) |
| | - DOUBLE OUTSWING DOOR |
| | - SINGLE OUTSWING FRENCH DOOR |
| | - SINGLE OUTSWING DOOR WITH HALF LITE |
| | - TOMB STONE FIXED GLASS WINDOWS (THE |
| | PROD. APP. THAT WAS SUBMITTED IS FOR |
| | CIRCLE TOP WINDOWS) |
| | - THE 96" X 80" FIXED GLASS WINDOW (#26) |
| | IS INCORRECTLY INDICATED ON THE PROD. |
| | APPROVAL CHART THAT WAS SUBMITTED. |
| | THIS SIZE IS NOT LISTED ON THE CHART |
| | AND IT EXCEEDS THE LARGEST SIZE THAT |
| | IS LISTED. |
| | |
| | 13) THE DOOR IN THE WALL BETWEEN THE |
| | GARAGE AND THE CONDITIONED SPACE IS |
| | REQUIRED TO BE SOLID CORE OR INSULATED |
| | PER FBC CHAPTER 13. PLEASE INDICATE ON |
| | PLANS. |
| | |
| | ROBERT MCDOUGAL |
| | BLDG. PLAN REVIEW |
| | (561)805-6714 |