| Plan Review Notes For Permit 03050843 |
| Permit Number |
03050843 |
|
| Review Stop |
B |
| Sequence Number |
3 |
|
| Notes |
| Date |
Text |
| 2003-07-03 00:00:00 | BUILDING REVIEW APPROVED WITH PROVISO: | | | 1-PROVIDE COMPLETE FRAMING DETAIL FOR | | | WINDOW SHOWING HOW FRAME IS REINFORCED | | | TO RECEIVE THE STORM SHUTTERS. SECTION | | | 104.2.1.2 CITY AMENDMENTS TO FBC 2001. | | | 2-PROVIDE COMPLETE WALL SECTION FOR | | | GABLE END WALL. SPECIFY ALL FASTENERS. | | | SEE SEC. 2313.4 FBC 2001. | | | 3-PRODUCT APPROVALS FOR DOORS & WINDOWS | | | SUBMITTED DON'T HAVE LEGIBLE DRAWINGS. | | | PLEASE, RESUBMIT PRODUCT APPROVALS | | | WITH LEGIBLE DRAWINGS. |
|