| Plan Review Notes For Permit 03050831 |
| Permit Number |
03050831 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2003-05-21 00:00:00 | | | | UNSAT | | | ~~~~~ | | | PLEASE NOTE THE FOLLOWING COMMENTS,MAKE | | | NECESSARY CORRECTIONS TO THE PLANS AND | | | RESUBMIT FOR REVIEW. | | | | | | 1} PLEASE NOTE THAT THE GROUNDING | | | ELECTRODE CONDUCTOR MUST COMPLY WITH | | | 250-50 INCLUDING THE FOOTER STEEL. | | | | | | 2} NOTE #17 INCORRECTLY REFERENCES THE | | | 1996 NEC.SHOULD REFERENCE THE 1999 NEC. | | | | | | 3} PLEASE SUBMIT AIC RATINGS FOR | | | ALL NEW EQUIPMENT BEING INSTALLED. | | | MAINS/PANELS/BREAKERS MUST BE RATED FOR | | | THE AVAILABLE FAULT CURRENT PER 110-9. | | | | | | 4} PLEASE LIST THE REQ'D BATH(S) | | | CIRCUIT(S). PER 210-11-C-3 | | | MUST BE 20A AND #12AWG. | | | | | | 5} PLEASE NOTE THAT ALL PLANS | | | DRAWN BY AN ARCHITECT/ENGINEER CONTAIN- | | | ING A TITLE BLOCK, MUST BE SIGNED, | | | DATED AND SEALED BY THE ARCH/ENGINEER OF | | | RECORD. PER FS/FAC 481.221 & 471.025 | | | | | | IF THERE ARE ANY QUESTIONS PLEASE CALL. | | | | | | BILL TROBAUGH | | | ELECTRICAL PLAN REVIEW | | | 561/805-6718 |
|