| Plan Review Notes For Permit 03050701 |
| Permit Number |
03050701 |
|
| Review Stop |
P |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2003-06-02 00:00:00 | DENIED | | | REFERENCE: FBC-2001 FUEL GAS | | | | | | 1) PIPING SHALL NOT BE INSTALLED IN | | | SOLID FLOOR SLABS. SEC 404.6 | | | 2) 1-1/4" PIPE REQUIRED FOR 200KBTU'S. | | | (SEE BBQ & RANGE) @ 125'. | | | 3) MINIMUM SIZE FOR 717K BTU'S @ 125' IS | | | 2". (2-1/2" SHOWN) | | | 4) IF THERE IS TO BE WELDED PIPING, THE | | | CERTIFICATION, & PICTURE I.D. OF THE | | | PERSON DOING THE WELDING SHALL BE SUB- | | | MITTED ALONG WITH THE WELDING PROCEDURE | | | PRIOR TO ISSUING PERMIT. (SHT P400 GAS | | | PIPING SPECIFICATIONS "A") | | | 5) FROM PREVIOUS REVIEW, PLEASE SUBMIT | | | CALCULATIONS FOR COMBUSTION AIR PER THE | | | FBC-2001 FUEL GAS CODE SEC. 304. | | | | | | REVIEW BY KEN STEVENS | | | (561) 659-8096 EXT 8377 | | | (561) 805-6721 | | | FAX (561) 653-2692 |
|