Plan Review Notes
Plan Review Notes For Permit 03050701
Permit Number 03050701
Review Stop P
Sequence Number 2
Notes
Date Text
2003-06-02 00:00:00DENIED
 REFERENCE: FBC-2001 FUEL GAS
  
 1) PIPING SHALL NOT BE INSTALLED IN
 SOLID FLOOR SLABS. SEC 404.6
 2) 1-1/4" PIPE REQUIRED FOR 200KBTU'S.
 (SEE BBQ & RANGE) @ 125'.
 3) MINIMUM SIZE FOR 717K BTU'S @ 125' IS
 2". (2-1/2" SHOWN)
 4) IF THERE IS TO BE WELDED PIPING, THE
 CERTIFICATION, & PICTURE I.D. OF THE
 PERSON DOING THE WELDING SHALL BE SUB-
 MITTED ALONG WITH THE WELDING PROCEDURE
 PRIOR TO ISSUING PERMIT. (SHT P400 GAS
 PIPING SPECIFICATIONS "A")
 5) FROM PREVIOUS REVIEW, PLEASE SUBMIT
 CALCULATIONS FOR COMBUSTION AIR PER THE
 FBC-2001 FUEL GAS CODE SEC. 304.
  