Plan Review Notes
Plan Review Notes For Permit 03050679
Permit Number 03050679
Review Stop B
Sequence Number 1
Notes
Date Text
2003-06-16 00:00:00BUILDING REVIEW APPROVED WITH PROVISO:
 1-REVISE SURVEY. LOT 67 IS WRITTEN TWICE
 ONE OF THEM NEED TO BE LOT 68.
 2-WINDOW 34SH IN BEDROOMS DOESN'T ALLOW
 THE 24" OPENING REQUIRED BY SECTION
 1005.4.4 FBC 2001. REVISE AS REQUIRED.
 3-REVISE TRUSS ANCHOR SCHEDULE AND ALL
 DETAILS THAT ARE AFFECTED BY SECTION
 1609.4.3 FBC 2001, WHICH DOESN'T
 ALLOW THE STEEL STRESS INCREASE.
 4-STORM PANELS INSTALLATION SCHEDULE:
 **ANCHORS TO BE SPACED 12" O.C. (NOT
 12.5") IF EDGE DISTANCE IS 2". REVISE
 AS REQUIRED.