| Plan Review Notes For Permit 03050679 |
| Permit Number |
03050679 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2003-06-16 00:00:00 | BUILDING REVIEW APPROVED WITH PROVISO: | | | 1-REVISE SURVEY. LOT 67 IS WRITTEN TWICE | | | ONE OF THEM NEED TO BE LOT 68. | | | 2-WINDOW 34SH IN BEDROOMS DOESN'T ALLOW | | | THE 24" OPENING REQUIRED BY SECTION | | | 1005.4.4 FBC 2001. REVISE AS REQUIRED. | | | 3-REVISE TRUSS ANCHOR SCHEDULE AND ALL | | | DETAILS THAT ARE AFFECTED BY SECTION | | | 1609.4.3 FBC 2001, WHICH DOESN'T | | | ALLOW THE STEEL STRESS INCREASE. | | | 4-STORM PANELS INSTALLATION SCHEDULE: | | | **ANCHORS TO BE SPACED 12" O.C. (NOT | | | 12.5") IF EDGE DISTANCE IS 2". REVISE | | | AS REQUIRED. |
|