| Plan Review Notes For Permit 03050619 |
| Permit Number |
03050619 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2003-05-19 00:00:00 | ************** UNSAT **************** | | | | | | 1)NOTE: PLEASE INDICATE IF PANEL "A" | | | IS MCB. 225-31, 240-3 | | | | | | 2)NOTE: PLEASE SUBIT AIC RATING(S) FOR | | | MAIN/ PANEL. 110-9/215-5 | | | | | | 3)NOTE: PLEASE LIST THE REQ`D ARC FAULT | | | PROTECTED CIRCUITS ON PANEL SCHEDULE. | | | 210-12 | | | | | | 4)NOTE: PLEASE LIST THE REQ`D BATH | | | CIRCUIT(S) ON PANEL SCHEDULE. 210-52D, | | | 210-11C3 | | | | | | 5)NOTE: PLEASE SEE MISSING SD`S IN ALL | | | SLEEPING ROOMS AND OUTSIDE ALSO. REQ`D | | | BY NFPA-72 8-1.4.2 | | | | | | 6)NOTE: PLEASE SEE MISSING GFI RECEPT | | | PER 210-52E | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-805-6717 | | | [email protected] |
|