| 2003-06-03 00:00:00 | UNSAT | | | ~~~~~ | | | PLEASE MAKE THE FOLLOWING CHANGES TO THE | | | PLAN FOR CODE COMPLIANCE. | | | | | | 1} PLEASE SUBMIT AIC RATINGS FOR | | | ALL NEW EQUIPMENT BEING INSTALLED. | | | MAINS/PANELS/BREAKERS MUST BE RATED FOR | | | THE AVAILABLE FAULT CURRENT PER 110-9. | | | | | | 2} PLEASE LIST THE REQ'D BATH(S) | | | CIRCUIT(S). PER 210-11-C-3 | | | MUST BE 20A AND #12AWG. | | | | | | 3} PLEASE LIST THE REQ'D ARC | | | FAULT PROTECTED CIRCUITS ON PANEL | | | SCHEDULE OR NOTE ON PLANS FOR BRANCH | | | CIRCUIT PROTECTION. PER 210-12 | | | | | | 4} SHOW SMOKE DETECTORS PER 8-1.4.2 | | | NFPA-72. | | | | | | 5} PLEASE NOTE THAT FUTURE FAN OUTLETS | | | SHOWN ARE NOT IN COMPLIANCE WITH THE | | | INTENT OF 210-70(A)(1). | | | | | | IF THERE ARE ANY QUESTIONS PLESE CALL. | | | | | | BILL TROBAUGH | | | ELECTRICAL PLAN REVIEW | | | 561/805-6718. |
|