2003-06-03 00:00:00UNSAT
 ~~~~~
 PLEASE MAKE THE FOLLOWING CHANGES TO THE
 PLAN FOR CODE COMPLIANCE.
  
 1} PLEASE SUBMIT AIC RATINGS FOR
 ALL NEW EQUIPMENT BEING INSTALLED.
 MAINS/PANELS/BREAKERS MUST BE RATED FOR
 THE AVAILABLE FAULT CURRENT PER 110-9.
  
 2} PLEASE LIST THE REQ'D BATH(S)
 CIRCUIT(S). PER 210-11-C-3
 MUST BE 20A AND #12AWG.
  
 3} PLEASE LIST THE REQ'D ARC
 FAULT PROTECTED CIRCUITS ON PANEL
 SCHEDULE OR NOTE ON PLANS FOR BRANCH
 CIRCUIT PROTECTION. PER 210-12
  
 4} SHOW SMOKE DETECTORS PER 8-1.4.2
 NFPA-72.
  
 5} PLEASE NOTE THAT FUTURE FAN OUTLETS
 SHOWN ARE NOT IN COMPLIANCE WITH THE
 INTENT OF 210-70(A)(1).
  
 IF THERE ARE ANY QUESTIONS PLESE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/805-6718.