| Plan Review Notes For Permit 03050613 |
| Permit Number |
03050613 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2003-05-19 00:00:00 | *************** UNSAT ************ | | | | | | 1)NOTE: PLEASE INDICATE MAIN FOR SERVICE | | | MCB?. 225-31, 240-3 | | | | | | 2)NOTE: PLEASE SUBMIT AIC RATING FOR | | | MAIN/ PANEL/ BRKRS MUST BE RATED FOR | | | THE AVAILABLE FAULT CURRENT.110-9/215-5 | | | | | | 3)NOTE: PLEASE LIST THE REQ`D ARC FAULT | | | PROTECTED CIRCUIT(S) 210-12 | | | | | | 4)NOTE: PLEASE SEE MISSING RECEPTS FOR | | | KITCHEN COUNTERSPACE PER 210-52C1 | | | | | | 5)NOTE: PLEASE LIST THE REQ`D BATH | | | CIRCUIT(S) PER 210-52D/210-11-C3 | | | | | | 6)NOTE: PLEASE SEE PANEL SCHEDULE, SHOWS | | | GARAGE DOOR OPENER? NO GARAGE ON PLANS? | | | PLEASE VERIFY. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-805-6717 | | | [email protected] |
|