Plan Review Notes
Plan Review Notes For Permit 03050608
Permit Number 03050608
Review Stop B
Sequence Number 3
Notes
Date Text
2004-01-14 00:00:00*****CORRECTIONS****
  
 REVISION #1
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 [email protected]
  
 1.)ZONING APPROVAL REQUIRED.
  
 2.)WHEN RESUBMITTING, SUBMIT OLD
 SHEETS.
  
 3.)SIGN THE OWNER/AGENT LINE OF THE
 ENERGY CALCS.
  
 4.)PLEASE NOTE THAT IF THE UNDER AIR
 AREA CHANGES, NEW ENERGY CALCS
 REFLECTING THE NEW CONDITIONED FLOOR
 AREA WILL BE REQUIRED.
  
 5.)PROVIDE A VALUE FOR THE ADDITIONAL
 SCOPE OF WORK.