| Plan Review Notes For Permit 03050588 |
| Permit Number |
03050588 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2003-06-16 00:00:00 | BUILDING REVIEW APPROVED WITH PROVISO: | | | 1-WINDOW 34SH FOR BEDROOMS DOESN'T | | | PROVIDE THE 24" CLEAR HEIGHT REQUIRED | | | BY SEC. 1005.4.4 FBC 2001. REVISE AS | | | REQUIRED. | | | 2-REVISE TRUSS ANCHOR SCHEDULE AND ALL | | | DETAILS THAT ARE AFFECTED BY SECTION | | | 1609.4.3 FBC 2001, WHICH DOESN'T | | | ALLOW THE STRESS INCREASE TO BE USED. | | | 3-STORM PANELS INSTALLATION SCHEDULE: | | | ANCHOR TO BE SPACED 12"O.C. MAXIMUM | | | WHEN EDGE DISTANCE IS LESS THAN 2". | | | SEE ENGINEERED DRAWINGS. |
|