2003-08-15 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
  
 1) FLOOR DRAIN IN EXISTING TRASH ROOM
 NOT VENTED. TABLE 906.1
 2) FLOOR DRAIN OUTSIDE NOT APPROVED. NO
 PROVISIONS SHOWN FOR KEEPING RAIN/STORM
 WATER OUT OF THE GREASE/SANITARY SYSTEM.
 SECTION 90-125(B)(5) CITY CODE.
  