2003-05-15 00:00:00************ UNSAT **************
  
 1)NOTE: PLEASE SEE MEANS OF EGRESS LT
 CONTROL FROM REC RM DOOR TO OUTSIDE
 WALK. S-4? TO BE ADDED? 210-70
  
 2)NOTE: PLEASE LIST THE REQ`D ARC FAULT
 PROTECTED CIRCUITS ON PANEL SCHEDULE
 210-12
  
 3)NOTE: PLEASE LIST THE REQ`D BATH CIR-
 -CUIT ON PANEL SCHEDULE 210-52D/210-11C3
 #12,20A
  
 4)NOTE: PLEASE SEE A COUPLE OF RECEPTS
 MISSING TO MEET 210-52/ OFFICE AND NEW
 BEDROOM.
  
 5)NOTE: PLEASE SEE FBC CHAPTER 34 FOR
 ADDITIONS TO EXISTING STRUCTURES. THE
 SQ FT BEING ADDED EXCEEDS % 3401.7.1.1
 PLEASE SHOW / CLARIFY ORIG ELECTRICAL
 AS EXISTING AND THAT IT MEETS CURRENT 99
 NEC FOR ELECTRICAL REQ`MENTS.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. PLEASE TAKE OUT ANY OLD/VOIDED
 SHEETS AND INSERT NEWSHEETS INTO TWO
 COMPLETE SETS FOR REVIEW AND STAMPING.
 IF THERE ARE ANY QUESTIONS, PLEASE CALL.
  