| Plan Review Notes For Permit 03050583 |
| Permit Number |
03050583 |
|
| Review Stop |
E |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2003-05-15 00:00:00 | ************ UNSAT ************** | | | | | | 1)NOTE: PLEASE SEE MEANS OF EGRESS LT | | | CONTROL FROM REC RM DOOR TO OUTSIDE | | | WALK. S-4? TO BE ADDED? 210-70 | | | | | | 2)NOTE: PLEASE LIST THE REQ`D ARC FAULT | | | PROTECTED CIRCUITS ON PANEL SCHEDULE | | | 210-12 | | | | | | 3)NOTE: PLEASE LIST THE REQ`D BATH CIR- | | | -CUIT ON PANEL SCHEDULE 210-52D/210-11C3 | | | #12,20A | | | | | | 4)NOTE: PLEASE SEE A COUPLE OF RECEPTS | | | MISSING TO MEET 210-52/ OFFICE AND NEW | | | BEDROOM. | | | | | | 5)NOTE: PLEASE SEE FBC CHAPTER 34 FOR | | | ADDITIONS TO EXISTING STRUCTURES. THE | | | SQ FT BEING ADDED EXCEEDS % 3401.7.1.1 | | | PLEASE SHOW / CLARIFY ORIG ELECTRICAL | | | AS EXISTING AND THAT IT MEETS CURRENT 99 | | | NEC FOR ELECTRICAL REQ`MENTS. | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. PLEASE TAKE OUT ANY OLD/VOIDED | | | SHEETS AND INSERT NEWSHEETS INTO TWO | | | COMPLETE SETS FOR REVIEW AND STAMPING. | | | IF THERE ARE ANY QUESTIONS, PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-805-6717 | | | [email protected] |
|