Plan Review Notes
Plan Review Notes For Permit 03050583
Permit Number 03050583
Review Stop B
Sequence Number 2
Notes
Date Text
2003-06-26 00:00:00******CORRECTIONS*******
  
 SAMANTHA THYNG, BUILDING PLANS EXAMINER
 [email protected]
  
 1.)SMOKE DETECTORS ON EXISTING HOUSE
 MUST COMPLY WITH FBC 905.2.2,
 FBC3401.7.1.2.
  
 2.)THE SURVEY SHOWS AN INCORRECT
 FLOOD ZONE DESIGNATION.PLEASE REVISE.
  
 3.)THE PLANS ARE STAMPED FOR IMPACT
 FEES BUT THE SQUARE FOOTAGE ON THE PLAN,
 2608, IS NOT CONSISTENT WITH THE
 AMOUNT ON THE STAMP (2393).233-5025
  
 4.)SEE THE PREVIOUS LIST, ITEM #13,
 REGARDING ATTACHMENTS F AND H (S3) NOT
 LISTED ON ANCHOR SCHEDULE (S2).
  
 5.)THE SITE PLAN, A1, SHOWS AN
 "EXISTING 2-STORY RESIDENCE".REVISE.
  
 6.)PROVIDE A SOILS INVESTIGATION
 REPORT.
  
 7.)THE CASEMENT WINDOW PRODUCT
 APPROVAL HAS SHEETS FOR A FIXED WINDOW
 IN IT; MULLION PRODUCT APPROVAL WAS
 NOT SUBMITTED; PRODUCT APPROVALS NOT
 LEGIBLE (SEE PREVIOUS CORRECTION NOTE
 #15).SEE WWW.MIAMIDADE.GOV (FIND A
 DEPARTMENT, BUILDING CODE COMPLIANCE,
 PRODUCT CONTROL) TO DOWNLOAD DADE
 COUNTY PRODUCT APPROVALS.
  
 WHEN RESUBMITTING, CLOUD OR OTHERWISE
 MARK ALL CHANGES.REPLACE SHEETS WHICH
 HAVE BEEN REVISED, AND ATTACH ONE COPY
 OF THE OLD SHEETS SEPARATELY.DO THIS
 FOR ALL SETS.