Plan Review Notes
Plan Review Notes For Permit 03050583
Permit Number 03050583
Review Stop B
Sequence Number 1
Notes
Date Text
2003-05-28 00:00:00********CORRECTIONS********
  
 1.)SIGN THE OWNER/AGENT LINE ON THE
 ENERGY CALC.
  
 2.)PROVIDE A COPY OF THE SURVEY
 REFERRED TO ON THE PLAN WITH ELEVATIONS,
 IF AVAILABLE.
  
 3.)THE AREA TABULATIONS (A2) SHOULD
 INCLUDE EXISTING AREAS, PROPOSED, AND
 NEW TOTALS.
  
 4.)THIS PROPERTY IS IN A FLOOD ZONE.
 THE FINISHED FLOOR ELEVATION IS
 REQUIRED TO BE 6" ABOVE THE BASE FLOOD
 ELEVATION (7'), CITY OF WEST PALM BEACH
 MUNICIPAL CODE 95-546.
  
 5.)ADDITIONAL FEES DUE, $543.97.
  
 6.)THE WINDOW AT THE SHOWER MUST
 COMPLY WITH FBC 2405.2.
  
 7.)THE ROOF SHEATHING (FOYER SECTION,
 A3, WALL SECTION A5) MUST COMPLY WITH
 CITY OF WEST PALM BEACH AMENDMENT TO
 THE FBC, TABLE 2306.1, ATTACHED.
  
 8.)THE SOFFIT VENTING IS REQUIRED
 TO COMPLY WITH FBC 2309.7, CANNOT
 "MATCH EXISTING" (FOYER SECTION, A3).
  
 9.)IMPACT FEES MUST BE PAID TO PALM
 BEACH COUNTY.THE PLANS MUST BE
 STAMPED AND THE RECEIPT ATTACHED TO THE
 APPLICATION.233-5025
  
 10.) ATTIC ACCESS REQUIRED, FBC2309.
  
 11.)PROVIDE A DETAIL FOR THE NEW
 FRAME WALL (A2 FLOOR PLAN).INSULATION
 IS REQUIRED BETWEEN CONDITIONED AND
 NON-CONDITIONED SPACE.
  
 12.)S2, ROOF FRAMING PLAN, SHOWS
 ATTACHMENT D, TARGET UPLIFT 2230 WHICH
 EXCEEDS THE MAX UPLIFT OF 1845 ON THE
 TRUSS ANCHOR SCHEDULE.
  
 13.)ATTACHMENTS F AND H, ROOF FRAMING
 PLAN (S3), ARE NOT LISTED ON THE
 ANCHOR SCHEDULE.
  
 14.)SHOW THE SOUTH PROPERTY LINE ON
 THE FOUNDATION PLAN.THE FOOTER FOR THE
 PRIVACY WALL CANNOT ENCROACH THE
 PROPERTY LINE.
  
 15.)SUBMIT TWO LEGIBLE COPIES OF THE
 FOLLOWING PRODUCT APPROVALS:
 FIXED GLASS WINDOW
 CASEMENT
 MULLION
 FRENCH DOORS
 SIDELITS
 GARAGE DOOR
 ROOF SHINGLES
 IMPACT PROTECTION