| Plan Review Notes For Permit 03050304 |
| Permit Number |
03050304 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2003-06-09 00:00:00 | *****CORRECTIONS******* | | | | | | SAMANTHA THYNG, BUILDING PLANS EXAMINER | | | [email protected] | | | | | | 1.)PROVIDE A DETAIL FOR THE FRAME | | | BEARING WALL (A2). | | | | | | 2.)THE WINDOW JAMB DETAIL CONFLICTS | | | WITH THE WINDOW PRODUCT APPROVAL (A6). | | | | | | 3.)UPLIFT SPECIFIED FOR TRUSS/GIRDER | | | CONNECTORS EXCEED PRODUCT LIMITATIONS. |
|