| Plan Review Notes For Permit 03050250 |
| Permit Number |
03050250 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2003-07-25 00:00:00 | ************** UNSAT ******************* | | | | | | 1)NOTE: PLEASE SEE ATTACHED COPY OF | | | FAC 61G1-16.004. PLEASE INCLUDE ALL | | | INFORMATION ON TITLE BLOCK. | | | | | | 2)NOTE: PLEASE SEE SIZING OF GROUNDING | | | ELECTRODE CONDUCTOR. IT APPEARS TO HAVE | | | CONDUCTOR SIZE REVERSED FOR CWP AND MAIN | | | GROUNDING ELECTRODE CONDUCTOR. | | | 250.66/ 310.15 | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-805-6717 | | | [email protected] |
|