| Plan Review Notes For Permit 03050246 |
| Permit Number |
03050246 |
|
| Review Stop |
M |
| Sequence Number |
5 |
|
| Notes |
| Date |
Text |
| 2005-04-11 00:00:00 | DENIED: | | | PLANS SUBMITTED AS A REVISION.THIS | | | SECTION OF THE BUILDING WAS NEVER | | | REVIEWED UNDER THE REFERENCED PERMIT | | | NUMBER.PLAN SHEET MEP1.1 INDICATES | | | "THIS SPACE TO BE BUILT UNDER SEPARATE | | | PERMIT". | | | | | | 1.PLEASE INDICATE LOCATION OF THE | | | CONDENSING UNIT.PROVIDE INFORMATION | | | FOR THE STAND IF LOCATED ON THE ROOF. | | | SHOW COMPLIANCE WITH 2001 FBC 1511.7. | | | | | | 2.INDICATE ACCESS TO THE ROOF. | | | | | | 4.FAN SHUTDOWN BY DUCT SMOKE DETECTOR | | | REQUIRED PER 2001 FBC/M606.2.1 AND | | | SHALL HAVE NOTIFICATION TO ALARM/STROBE | | | IN NORMALLY OCCUPIED AREAS 606.4.1 #2. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | | CONTACT PATTY KRAUSS AT (561)805-6719. |
|