| 2005-04-04 00:00:00 | ******* UNSAT ********* |
| | |
| | 1)NOTE: PLEASE SEE REVISION TO SPACE IS |
| | TO BE SUBMITTED UNDER A SEPARATE PERMIT |
| | AS NOTED ON ORIGINAL BLDG PLANS. |
| | |
| | 2)NOTE: PLEASE ALSO SUBMIT REVISED |
| | PLANS/RISER FOR BASE BLDGS. |
| | |
| | 3)NOTE: PLEASE SEE EQUIPMENT GROUNDING |
| | CONDUCTORS ARE ONLY INSTALLED AFTER THE |
| | FIRST MEANS OF DISCONNECT. 250.6,250.24 |
| | |
| | 4)NOTE: PLEASE SEE MIN GROUNDING |
| | ELECTRODE CONDUCTOR PER 250.66. |
| | THIS WAS ON ORIG THREE REVIEWS AND |
| | REDLINED ON PERMITTED PLANS. |
| | 250.66 MIN 1/0 (MISPRINT)? |
| | |
| | 5)NOTE: PLEASE VERIFY LOCATION OF NEW |
| | TRANSFER SWITCH. PLEASE SHOW AS EITHER |
| | MANUAL?AUTO? PLEASE SUBMIT SPECS |
| | SHEETS FOR TRANSFER SWITCH, SHOWONG IF |
| | IT IS "SERVICE ENT RATED" |
| | PLEASE VERIFY IF TRANSFER SWITCH IS |
| | INDEED ON LOAD SIDE OF SERVICE DISC? |
| | |
| | 6)NOTE: PLEASE INCLUDE ALL CONDUCTORS |
| | FROM GUTTER TO MAINS ETC. |
| | 215.5,310.16 |
| | |
| | PLEASE SEE POSSIBLE COMMENTS FROM OTHER |
| | REVIEWERS WHICH MAY AFFECT ELECTRICAL |
| | PLANS. |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. IF THERE ARE ANY QUESTIONS, |
| | PLEASE DO NOT HESITATE TO CALL. |
| | |