| 2003-12-24 00:00:00 | 1) THE FIRE DEPARTMENT CONNECTION SHALL | | | BE PROVIDED WITH 7'- 6" CLEARANCE. | | | | | | 2) THE FIRE DEPARTMENT CONNECTION SHALL | | | BE WITHIN 150 FEET OF A FIRE HYDRANT. | | | | | | 3) SEPARATE PLANS AND PERMITS REQUIRED | | | FOR FIRE SPRINKLER SYSTEM REMODEL. THE | | | FIRE SPRINKLER SYSTEM AND ANY FIRE | | | ALARM SYSTEM EQUIPMENT MUST BE UL | | | LISTED FOR CENTRAL STATION SERVICE SINCE | | | THIS BECAME EFFECTIVE AUGUST 1, 2003. | | | | | | 4) THE DESIGN TEAM AND OWNER RED-LINED | | | THE DRAWINGS ON 12-24-03 AND MADE | | | CORRECTIONS TO THE DRAWINGS. | | | | | | 5) THE BACKFLOW DEVICE FOR THE FIRE | | | SPRINKLER SYSTEM IS REQUIRED TO HAVE | | | TAMPER SWITCHES AND A CHAIN AND LOCK. | | | | | | MIKE CARSILLO, ASSISTANT FIRE MARSHAL | | | BUREAU OF FIRE PREVENTION |
|