| Plan Review Notes For Permit 03050246 |
| Permit Number |
03050246 |
|
| Review Stop |
FIRE |
| Sequence Number |
3 |
|
| Notes |
| Date |
Text |
| 2003-11-24 00:00:00 | 1) ONE HOUR DOORS STILL SHOWN AT THE | | | GARAGE. THESE DOORS SHALL BE AT LEAST | | | 1 1/2 HOURS SINCE THE WALLS ARE | | | REQUIRED TO BE AT LEAST TWO HOUR | | | FIRE RATED. | | | | | | 2) DOORS # 13 AND 17 SHALL BE 45 MINUTE | | | FIRE RATED. STORAGE IS NOT PERMITTED | | | UNDER STAIRS UNLESS THE STORAGE AREA | | | IS RATED THE SAME AS THE REQUIRED | | | RATING FOR THE STAIRS. | | | | | | 3) DOOR HARDWARE ON DOORS # 23 AND 26 | | | SHALL NOT REQUIRE THE USE OF A KEY, | | | TOOL, SPECIAL KNOWLEDGE OR EFFORT. | | | DOOR # 23 CANNOT BE LOCKABLE FROM | | | WITHIN THE OFFICE. | | | | | | 4) KNOX-BOX SHOULD BE INSTALLED ON | | | ELEVATION WHERE THE ADDRESS IS LOCATED. | | | | | | 5) FIRE SPRINKLER PLANS ARE REQUIRED | | | AT TIME OF PERMIT. SHOP DRAWINGS | | | ARE REQUIRED LATER. | | | | | | MIKE CARSILLO, ASSISTANT FIRE MARSHAL | | | 835-2910 |
|