| Date |
Text |
| 2003-10-01 00:00:00 | DENIED |
| | REFERENCE: FBC-2001 PLUMBING |
| | FBC-2001 CHAPTER 1 |
| | FBC-2001 CHAPTER 11 |
| | FBC-2001 BUILDING |
| | FLORIDA ADMIN. CODE |
| | A) FOLLOWING COMMENTS HAVE NOT BEEN |
| | ADDRESSED FROM PREVIOUS REVIEW. THE |
| | NUMBER SHALL STAY THE SAME FOR CLAIRITY. |
| | 1) PLEASE SUBMIT CALCULATIONS FOR MINI- |
| | MUM FACILITIES. TABLE 403.1 - INDICATE |
| | TOTAL AREA FOR EACH OCCUPANCY AND TOTAL |
| | FIXTURES REQUIRED FOR EACH OCCUPANCY. |
| | 2) IF BATHING ROOMS ARE PROVIDED, THEN |
| | EACH PUBLIC AND COMMON USE BATHING FAC- |
| | ILITY SHALL COMPLY WITH 11-4.23. SECTION |
| | 11-4.1.2(6). |
| | 3) SHT A1.0 LOUNGE AND KITCHEN SINKS |
| | SHALL COMPLY WITH 11-4.24 AND ALL SUB- |
| | SECTIONS. PLEASE PROVIDE DETAILS. |
| | 4) SHT A1.0 ALL TOILET ROOMS SHALL |
| | COMPLY WITH 11-4.24, 11-4.16, 11-4.19 |
| | AND ALL SUBSECTIONS. PLEASE PROVIDE DE- |
| | TAILS. |
| | 5) SHT A1.1 SEE COMMENT #4. |
| | 6) SHT A1.2 SUBMIT CALCULATIONS FOR ROOF |
| | GUTTER AND SOWNSPOUTS. SHOW TOTAL SQUARE |
| | FOOTAGE FOR EACH ROOF AREA. AREA OF UP- |
| | PER ROOF THAT DRAINS TO LOWER ROOF SHALL |
| | BE ADDED WHEN SIZING GUTTERS AND DOWN- |
| | SPOUTS. SHOW IN CALCULATIONS. ALSO SHOW |
| | 1/2 AREA OF ALL VERTICAL WALLS INCLUDING |
| | PARAPETS ADD TO CALCULATIONS. TABLE |
| | 1106.2 AND TABLE 1106.6. INDICATE PITCH |
| | (SLOPE) OF GUTTER, AND SHOW WHERE THE |
| | PITCH TO EACH DOWNSPOUT STARTS. |
| | 7) DOWNSPOUTS SHALL TERMINATE A MINIMUM |
| | OF 1' FROM THE STRUCTURE SIDEWALL. SEC |
| | 1503.4.4. PROVIDE A DETAIL. |
| | 11) SHT MEP3.0 SANT RISER DIAGRAM, ONLY |
| | FIXTURES FROM THE BATHROOM GROUP SHALL |
| | DRAIN THROUGH THE HORIZONTAL WET VENT. |
| | SEC 909.1. 1ST FLOOR KITCHEN SINK SHALL |
| | CONNECT DOWNSTREAM OF THE TOILET ROOM |
| | FIXTURES. SEPARATE STACK FOR KITCHEN |
| | SINK REQUIRED. |
| | 12) SUPPLY TO HOSE BIBB IN ELECTRICAL |
| | ROOM IS NOT SHOWN ON SHT MEP2.3 NOR SHT |
| | MEP3.0 RISER.104.2.1 |
| | NEW COMMENTS: |
| | 13) SECTION 606.2(2) SHUTOFF VALVE RE- |
| | QUIRED FOR HOSE BIBB. |
| | 14) PLEASE BE AWARE OF FF 553.80(2)(B) |
| | CONCERNING DESIGN PROFESSIONALS AND PLAN |
| | REVIEWS. |
| | |
| | ---------WHEN RESUBMITTING PLANS-------- |
| | PLEASE CLEARLY INDICATE THE REVISION AND |
| | REMOVE AND REPLACE ANY PAGES AS NECESS- |
| | ARY. SUBMIT (1) SET OF OLD DRAWINGS WITH |
| | THE PLANS WHEN RESUBMITTING PLANS. A |
| | TRANSMITTAL LETTER LISTING THE ORIGINAL |
| | REVIEW NUMBER, WITH A DESCRIPTION OF THE |
| | REVISION MADE, IDENTIFYING THE SHEET OR |
| | SPECIFICATION PAGE WHERE THE CHANGES CAN |
| | BE FOUND, WILL HELP TO EXPEDITE YOUR |
| | PERMIT. THANK YOU FOR YOUR ANTICIPATED |
| | COOPERATION. |
| | |
| | REVIEW BY KEN STEVENS |
| | (561) 805-6721 |
| | FAX (561) 653-2692 |
| | E-MAIL [email protected] |