| Plan Review Notes For Permit 03050246 |
| Permit Number |
03050246 |
|
| Review Stop |
M |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2003-09-24 00:00:00 | DENIED: | | | 1. PLEASE CLARIFY OUTSIDE AIR TO AHU-1. | | | NOTE ON PLAN SHEET MEP 2.1 INDICATES | | | O.A. AT CEILING OF THE FIRE PUMP ROOM. | | | OUTSIDE AIR NEEDS TO COME FROM OUTSIDE | | | THE BUILDING. INTAKE OPENING SHALL BE | | | LOCATED A MINIMUM OF 10 FT FROM LOT LINE | | | OR BUILDINGS ON THE SAME LOT (2001 FBC/M | | | 401.5.) | | | | | | CLARIFY RETURN AIR FOR AHU-1. WILL THE | | | MECHANICAL ROOM BE USED AS A PLENUM? | | | MECHANICAL CLOSETS/ROOMS TO COMPLY WITH | | | 2001 FBC CHAPTER 13 SUB-SECTION 410.1.AB | | | 410.1.ABCD.3.7. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | | CONTACT PATTY KRAUSS AT (561) 805-6719. |
|