| 2003-09-29 00:00:00 | ************* UNSAT ******************* |
| | |
| | PLEASE SEE THAT SOME NOTES FROM FIRST |
| | REVIEW NEED TO BE ADDRESSED. |
| | |
| | 1)NOTE: PLEASE SHOW ALL CIRCUITING ON |
| | PLANS AND CORRELATE WITH PANEL SCHEDULES |
| | SUBMITTED. |
| | IE, ACCU-1 ON ROOF SHOWN ON GFI RECEPT |
| | CIRCUIT. PLEASE GO THROUGH OTHERS. |
| | |
| | 2)NOTE: PLEASE SEE 700.12E FOR CIRCUIT- |
| | -ING OF EM/EXT LTS. |
| | PLEASE ALSO SEE 700.16 STAIRWAY? |
| | |
| | 3)NOTE: PLEASE SEE SERVICE LOCATION |
| | OUTSIDE, APPEARS TO ONLY SHOW ONE METER |
| | AND THREE PANELS/ORDISCS. |
| | |
| | 4)NOTE: PLEASE SEE /CLARIFY MEANS OF |
| | EEQUIPMENT GROUNDING FROM MAIN DISC'S TO |
| | PANELS. 250.24/250.110/250.122 |
| | |
| | 5)NOTE: PLEASE CLARIFY LOCATION OF REQ'D |
| | SIGN CIRCUIT 600.5 |
| | |
| | 6)NOTE: PLEASE SEE FIRE PLAN REVIEW |
| | NOTES THAT WILL HAVE AN AFFECT ON |
| | ELECTRICAL PLANS. |
| | |
| | 7)NOTE: CIRCUIT FOR OUTSIDE WALLPACKS |
| | IS NOW SHOWN ,HOWEVER HOW ARE THESE |
| | CONTROLLED? PC/TC? ARE THEY ON 24/7? |
| | |
| | 8)NOTE: PLEASE CLARIFY WHAT APPEARS TO |
| | BE A FAN OUTSIDE NEXT TO SERVICE? |
| | |
| | 9)NOTE: PLEASE CORRELATE SYMBOLS FOR |
| | EXIT LTS AND ANY OTHERS. |
| | PLEASE CLARIFY MEANS OF LIGHTING STAIR- |
| | WAY. LS 101 5-8 |
| | |
| | 10)NOTE: PLEASE SEE ATTACHED COPY OF |
| | FS 553.80(2)(B) WITH RESPECT TO DESIGN |
| | PROFESSIONALS. |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. IF THERE ARE ANY QUESTIONS, |
| | PLEASE CALL. |
| | |
| | PLEASE NOTE, MAX FUTURE TENANT TO BE |
| | 100A'S. |
| | |