| Date |
Text |
| 2003-06-04 00:00:00 | DENIED |
| | REFERENCE: FBC-2001 PLUMBING |
| | FBC-2001 CHAPTER 11 |
| | |
| | 1) PLEASE SUBMIT CALCULATIONS FOR MINI- |
| | MUM FACILITIES. TABLE 403.1 - INDICATE |
| | TOTAL AREA FOR EACH OCCUPANCY AND TOTAL |
| | FIXTURES REQUIRED FOR EACH OCCUPANCE. |
| | (ALSO SEE TABLE 1003.1 BLDG CODE) |
| | 2) IF BATHING ROOMS ARE PROVIDED, THEN |
| | EACH PUBLIC AND COMMON USE TOILET ROOM |
| | SHALL COMPLY WITH 11-4.23 |
| | 3) SHT A1.0 LOUNGE AND KITCHEN SINKS |
| | SHALL COMPLY WITH 11-4.24 AND ALL SUB- |
| | SECTIONS. PLEASE PROVIDE DETAILS. |
| | 4) SHT A1.0 ALL TOILET ROOMS SHALL SHOW |
| | LENGTH AND WIDTH ON PLANS. ALL TOILET |
| | ROOMS SHALL COMPLY WITH 11-4.22 AND ALL |
| | SUBSECTIONS. PLEASE PROVIDE DETAILS. |
| | 5) SHT A1.1 - SEE COMMENT #4. |
| | 6) SHT A1.2 SUBMIT CALCULATIONS FOR ROOF |
| | GUTTER AND DOWNSPOUTS. SHOW SQUARE FOOT- |
| | AGE FOR EACH ROOF AREA. AREA OF UPPER |
| | ROOF THAT DRAINS TO LOWER ROOF SHALL BE |
| | ADDED WHEN SIZING GUTTERS AND DOWNSPOUTS |
| | OF LOWER ROOF. BE SURE TO SHOW THIS IN |
| | THE CALCULATIONS. TABLE 106.2 & TABLE |
| | 1106.6. INDICATE PITCH OF GUTTER, AND |
| | SHOW WHERE THE PITCH TO EACH DOWNSPOUT |
| | STARTS. |
| | 7) DOWNSPOUTS SHALL TERMINATE A MINIMUM |
| | OF 1' FROM BLDG WALL. SEC 1503.4.4 |
| | 8) SHT A1.2 SHOWS ROOF DRAIN ON RIGHT |
| | SIDE OF LOWER ROOF. IT STATES SEE MECH. |
| | DRAWINGS. UNABLE TO LOCATE ON MECH. |
| | DRAWINGS. PLEASE CLAIRFY. |
| | 9) SHT MEP2.4 PLUMBING NOTES #16, SEPAR- |
| | ATE PERMIT/PLANS REQD. FOR GAS. 104.1.1 |
| | 10) SHT MEP3.0 WATER HEATER IN LOUNGE TO |
| | BE ACCESSIBLE. SEC 501.4 - SUBMIT DETAIL |
| | 11) SHT MEP3.0 SANT RISER DIAGRAM, ONLY |
| | FIXTURES FROM THE BATHROOM GROUP SHALL |
| | DRAIN THROUGH THE HORIZONTAL WET VENT. |
| | SEC 909.1 - 1ST FLOOR KIT. SINK, SECOND |
| | FLOOR LOUNGE, & SECOND FLOOR BATHROOM |
| | SHALL ALL TIE IN DOWNSTREAM OF WET VENT. |
| | 12) SHT MEP3.0 WATER RISER DIAGRAM, 1ST |
| | FLOOR W/C AND LAV NOT SHOWN ON RISER. |
| | HOSE BIBB IN ELECTRIC ROOM? PLEASE |
| | CLAIRFY. IF H.B. IS FOR GROUND A HARD |
| | CAP IS SUGGESTED. NO SUPPLY TO H.B. IS |
| | SHOWN ON RISER DIAGRAM. |
| | |
| | REVIEW BY KEN STEVENS |
| | (561) 659-8096 EXT 8377 |
| | (561) 805-6721 |
| | FAX (561) 653-2692 |