| 2003-05-19 00:00:00 | DENIED:MECHANICAL PERMIT 03050253 |
| | |
| | 1.PLEASE PROVIDE OUTSIDE AIR CALCS |
| | AS PER 2001 FBC(M) TABLE 403.3. |
| | |
| | 2.PROVIDE CALCULATIONS FOR AIR CHANGES |
| | IN GARAGE AREA AS PER TABLE 403.3. |
| | |
| | 3.PLAN SHEET MEP3.0 INDICATES EF-1 |
| | TO RUN 15 MINUTES PER HOUR.AS PER 2001 |
| | FBC(M) 403.4 MECHANICAL VENTILATION NOT |
| | REQUIRED TO RUN CONTINUOUSLY WHERE THE |
| | SYSTEM IS ARRANGED TO OPERATE AUTO- |
| | MATICALLY UPON DETECTION OF A CONCENTRA- |
| | TIONOF CARBON MONOXIDE OF 25 (PPM) BY |
| | APPROVED AUTOMATIC DETECTION DEVICES. |
| | |
| | 4.CONDENSER UNIT STANDS ON ROOF SHALL |
| | COMPLY WITH 2001 FBC 1511.7 FOR THE |
| | DISTANCE BETWEEN THE ROOF FINISHED |
| | SURFACE AND THE BOTTOM OF THE SUPPORT |
| | RAIL. |
| | |
| | 5.FIRE DAMPERS ARE NOT INDICATED ON |
| | PLAN.PLEASE NOTE, FIRE DAMPERS ARE |
| | REQUIRED WHERE DUCTS PENETRATE A FIRE |
| | RATED WALL PARTITION OR FLOOR.PLEASE |
| | SHOW LOCATIONS OF ALL FIRE DAMPERS THAT |
| | ARE REQUIRED.2001 FBC(M) 607.6 |
| | |