| 2003-06-09 00:00:00 | PLEASE PROVIDE A COPY OF THE PAID |
| | IMPACT FEE RECEIPT FROM PALM BEACH |
| | COUNTY. |
| | |
| | THE BUILDING WILL BE LOCATED IN AN A8 |
| | FLOOD ZONE WITH AN 15.0' BASE FLOOD |
| | ELEVATION RELATIVE TO NGVD. |
| | |
| | THE BUILDING WILL BE A TWO STORY MIXED |
| | OCCUPANCY OF B/M/S. |
| | |
| | PLEASE SHOW A LAYOUT OF THE PROPOSED |
| | RACK STORAGE CALLED OUT ON SHEET A1.0 |
| | SO THA EGRESS REQUIREMENTS MAY BE |
| | DETERMINED. ALSO, INDICATE THE |
| | QUANTITIES AND NATURE OF THE |
| | COMMODITIES TO BE STORED.SEE FBC |
| | 104.2. |
| | |
| | WHAT WILL THE ROOM SHOWN AS |
| | "CONSTRUCTION" BE USED FOR?WHERE IS |
| | THE EXIT DOOR? |
| | |
| | IS THE AREA SHOWN AS "CONCRETE LID" ON |
| | SHEET A2.0 INTENDED FOR STORAGE OR |
| | ANOTHER OCCUPANCY/USE?IF SO INDICATE |
| | THE MINIMUM DESIGN LOADS AND |
| | ACCESS/EGRESS. |
| | |
| | PLEASE PROVIDE DETAILS FOR THE STAIRS |
| | INCLUDING RISE, RUN, HANDRAILS, FIRE |
| | RATED ENCLOSURE PROTECTION,DESIGN |
| | LOADS AND CONNECTION DETAILS. |
| | |
| | SHEET S1.1.SHOW THE DIMENSIONS FOR |
| | THESECOND FLOOR BALCONY AND THE GUARD |
| | RAIL DETAILS. |
| | |
| | SHOW HOW HURRICANE MISSILE IMPACT |
| | RESISTANCE WILL BE ACCOMPLISHED FOR THE |
| | EXTERIOR GAZED PORTIONS OF THE |
| | BUILDINGS.SEEFBC 1606.1.4. |
| | |
| | PROVIDE THE STRUCTURAL INFORMATION ON |
| | THE PLANS CALLED FOR IN FBC 1606.1.7. |
| | |
| | PLEASE PROVIDE THE ROOF COVERING DETAILS |
| | IN ACCORDANCE WITH FBC 104.2.1.1. |
| | |
| | SHOW THE END BEARING DETAIL AND |
| | CONNECTION FOR THE BAR JOISTS. |
| | |
| | SHEET S1.1.HOW IS THE TS COLUMN |
| | ATTACHED TO THE WF BEAM? |
| | |
| | SHOW THE DESIGN SPECIFICATIONS FOR THE |
| | PRECAST CONCRETE AND THE CONNECTION |
| | BEARING DETAILS. |
| | |
| | SHOW A REINFORCEMENT DETAIL FOR THE |
| | CANTILEVERED 6" SLAB AND THE BALCONY. |
| | |
| | SHOW THE FIRE RATED DOORS FOR THE STAIR |
| | SHAFTS.SEE FBC TABLE 705.1.2. |
| | |
| | SHOW THE FIRE DESIGN NUMBER(S) FOR THE |
| | STAIR AND ELEVATOR SHAFTS. |
| | |
| | SHOW THE FIRE SEPARATION, AND FIRE |
| | DESIGN NUMBER FOR THE MIXED OCCUPANCY |
| | SEPARATION.SEE FBC 704.1.1. |
| | |
| | SHOW THE INSTALLATION INFORMATION FOR |
| | THE GLASS BLOCK.SEE FBC 2112.5. |
| | |
| | PLEASE PROVIDE SPECIFIC DESIGN |
| | INFORMATION FOR THE "UNISTRUT WITH 5/8 |
| | GYP BOARD" SHOWN ON SHEET A2.0. |
| | |
| | S1.1 AND S1.2.HOW IS THE TOP OF THE |
| | PARAPET WALL FINISHED?LATERAL |
| | REINFORCEMENT? |