Plan Review Notes
Plan Review Notes For Permit 03050241
Permit Number 03050241
Review Stop P
Sequence Number 2
Notes
Date Text
2003-08-13 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
  
 1) SHEET P.7.0.1 (PHE) SECTION 909.1
 ONLY THE FIXTURES WITHIN THE BATHROOM
 GROUP SHALL CONNECT TO THE WET-VENTED
 HORIZONTAL BRANCH DRAIN. ANY ADDITIONAL
 FIXTURES SHALL DISCHARGE DOWNSTREAM OF
 THE WET VENT.-BAR SINK SHALL DIS-
 CHARGE DOWNSTREAM OF BATHROOM GROUP.
  
 2) SHEET P.7.0.2 UNABLE TO LOCATE THE
 REVISION ON THIS SHEET. INDICATE LOCAT-
 ION OF REVISION BY CLOUDING AND DARTING
 REVISION.
  
 3) ALL CHANGES OF THE FLOOR PLAN SHALL
 BE REFLECTED ON THE SANITARY RISER DIA-
 GRAM FOR THIS UNIT. SUBMIT REVISION FOR
 SANITARY RISER DIAGRAM.
  