| Plan Review Notes For Permit 03050241 |
| Permit Number |
03050241 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2003-05-08 00:00:00 | PROVISO:MECHANICAL PERMIT 03050491 | | | | | | PLAN SHEET A.4.1.1 MECH RM #E32, FLOOR | | | PLAN IN THE HALL INDICATES A 1 HR RATED | | | CEILING UP TO THE DOOR."A" DRAWINGS | | | CONFLICT WITH "P" & "M" DRAWINGS AS TO | | | THE LOCATION OF THE DOOR.PLANS DO NOT | | | INDICATE FIRE DAMPER, THIS IS APPROVED | | | SO LONG THE RATING DOES NOT CONTINUE | | | ABOVE THE RATED CEILING.PLEASE CLARIFY | | | | | | PLEASE NOTE, LAUNDRY RM MUST HAVE | | | HAVE GREATER THAN 800 CU FT FOR | | | COMBUSTION AIR FOR THE GAS DRYER. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | | CONTACT PATTY KRAUSS AT (561) 805-6719. |
|