| Plan Review Notes For Permit 03050237 |
| Permit Number |
03050237 |
|
| Review Stop |
P |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2003-06-06 00:00:00 | DENIED | | | REFERENCE: FBC-2001 PLUMBING | | | FBC-2001 CHAPTER 11 | | | | | | 1) SHT A-2.01 TOILET ROOM IN SALES OFF- | | | ICE SHALL COMPLY WITH SECTION 11-4.22 | | | AND ALL SUBSECTIONS. PLEASE SUBMIT A | | | DETAIL. 11-4.1.3(11) | | | 2) SHT A-2.01 KIT SINK SHALL COMPLY | | | WITH SECTION 11-4.24 AND ALL SUBSECIONS. | | | PLEASE SUBMIT A DETAIL. SINK SHALL BE | | | CENTERED ON THE 48" OF THE 30X48 CLEAR | | | FLOOR SPACE FOR PARRALEL APPROACH. | | | 3) SHT A-2.01 A DRINKING FOUNTAIN IS RE- | | | QUIRED PER TABLE 403.1. ALSO SEE SECTION | | | 410.1. | | | 4) SHT P-101 SANT. RISER DIAGRAM, KIT. | | | SINK SHALL NOT DRAIN INTO THE WET VENT | | | OF THE BATHROOM FIXTURES. SECTION 909.1 | | | SINK SHALL TIE IN DOWNSTREAM OF THE BATH | | | ROOM FIXTURES. | | | 5) SHT P-101 WATER RISER DIAGRAM, AIR | | | CHAMBERS ARE NOT APPROVED. PLEASE DE- | | | LEATE FROM RISER. SECTION 604.9 | | | 6) SHT A-2.01 IS MISLABLED AS STORAGE | | | BLDG FLOOR PLAN/ELEVATIONS/REFLECTED | | | CEILING PLANS ECT. | | | | | | REVIEW BY KEN STEVENS | | | (561) 659-8096 EXT 8377 | | | (561) 805-6721 | | | FAX (561) 653-2692 |
|