| Plan Review Notes For Permit 03050148 |
| Permit Number |
03050148 |
|
| Review Stop |
P |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2004-02-20 00:00:00 | | | | | | | | | | | | | PASSED/PROVISO | | | ACCORDING TO SIZING FORMULA FOR WATTS | | | EXPANSION TANKS, THE SIZE FOR THE EX- | | | PANSION TANK IS INSUFFICIENT FOR THE | | | AMOUNT OF GALLONS TOTALED FOR ALL W/H'S | | | (SEE ATTACHED SHEETS). THIS SHALL BE | | | ADDRESSED BY PLUMBING FINAL. | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | Z |
|