Plan Review Notes
Plan Review Notes For Permit 03050148
Permit Number 03050148
Review Stop P
Sequence Number 1
Notes
Date Text
2003-12-16 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FLA. ADMIN. CODE
 FLA. STATUTES
  
 1) SHTS P-U1 THRU P-U6 WATER RISER DIA-
 GRAMS, A WATER HAMMER ARRESTOR IS REQ-
 UIRED FOR THE ICE MAKER LINE TO THE REF-
 RIDGEERATOR. (NOT IN CEILING-PDI-WH 201
 AND MANUF. INSTALL. INSTRUCT. 604.9)
 2) SHT P-T3.3 THERMAL EXPANSION CONTROL
 NOT PROPERLY ADDRESSED WITH THE 3/4"
 VALVE AT THE BACKFLOW. 607.3.2
 3) ENGINEERS SHALL SUBMIT SIGNATURE ON
 SEAL. FAC 61G15-23.002(1) & FS 471.025.
 INITIALS NOT ACCEPTABLE PER FBPE AND
 BLDG OFFICIAL.
  